{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0AA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0AA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0AA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0AA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-0AA15, for transformer protection, CLASS 10 trip, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The Siemens SIRIUS 3RV2411-0AA15 is a circuit breaker designed specifically for transformer protection, not general motor or feeder duty. That means its trip curve and thermal memory are tuned to handle the inrush and magnetizing current of a transformer without nuisance tripping, while still clearing a winding fault fast. Rated breaking capacity hits 100 kA at 400 V AC — that's the fault current it can safely interrupt without welding contacts or venting arc plasma into the panel. It carries a CLASS 10 trip characteristic, so it will open within 10 seconds at 600% of the thermal setting, which is standard for protecting transformers against sustained overloads. ## Mounting and integration Mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. The 45 mm width (three module spaces) and 97 mm depth fit a standard distribution board or control panel without overhang. Any mounting position is allowed, so you can orient it vertically or horizontally in a tight gland plate layout. Terminals accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²) — sized for the control transformer primary side wiring typical in MCC buckets. ## Key ratings and what they mean Phase failure detection is built in — if one phase drops out on the primary side, the breaker trips, preventing single-phasing damage to the transformer. The rated insulation voltage spans 20 to 690 V, covering most low-voltage distribution systems up to 690 V line-to-line. Ambient operating range is -20 to +60 °C, with storage from -50 to +80 °C, so it handles unheated warehouses and panel heat rise without derating.","metaTitle":"Siemens 3RV2411-0AA15 SIRIUS Circuit Breaker, Transformer Pr","metaDescription":"Siemens SIRIUS 3RV2411-0AA15 circuit breaker for transformer protection. CLASS 10 trip, 100 kA breaking capacity at 400 V. Screw/snap-on 35 mm DIN rail. Active production. Quoted t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2411-0AA15","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for transformer protection A-release 0.11...0.16 A N-release 3.3 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.16 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.16 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.16 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.16 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.16 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 ... 14), 2x 12","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$41.91","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/616a95946db0da0fa467dd488f193543.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=406574&mlfb=3RV2411-0AA15"},"ai":{"faq":[{"question":"Where can I buy 3RV2411-0AA15 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3RV2411-0AA15's listed depth and width?","answer":"Depth is 97 mm, width is 45 mm (three 15 mm DIN module spaces), and height is 97 mm. These dimensions allow it to fit standard 35 mm DIN rail enclosures without overhang."},{"question":"Will 3RV2411-0AA15 drop into a panel specified around 3RV2011-0AA10 without rewiring?","answer":"Both mount on 35 mm DIN rail per DIN EN 60715 and share the same 45 mm width footprint. The terminal specification (screw-type, accepting 2x 0.5–2.5 mm²) is identical, so mechanical fit and wire termination are compatible. However, the 3RV2411-0AA15 is designed for transformer protection with a CLASS 10 trip characteristic, while the 3RV2011-0AA10 is a general motor-protective breaker — verify the trip curve matches your load before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0AA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0AA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}