{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0AA20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0AA20","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0AA20","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0AA20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-0AA20, Size S00, for transformer protection, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mount.","salesMarkdown":"It mounts on a 35 mm DIN rail per DIN EN 60715 using either screws or the integrated snap-on clip, and the Size S00 frame keeps the footprint compact at 45 mm wide by 97 mm deep. No ground fault detection on this variant, so if that's required, you'd need a separate GFCI or a different order code. Mounting position is any, so vertical or horizontal panel layouts work. Clearance: 50 mm above and below, 30 mm to the side, zero forward or backward — that's tight enough for dense DIN-rail packing but leaves room for wiring fingers. Use a 3 mm diameter screwdriver with a 3.0 × 0.5 mm tip for the terminal screws.","metaTitle":"Siemens 3RV2411-0AA20 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2411-0AA20 SIRIUS circuit breaker for transformer protection. Trip Class 10, 100 kA breaking capacity at 400 V AC. Size S00, screw and snap-on DIN rail mount. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.16 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.16 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.16 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.16 A","at AWG cables for main contacts":"2x (20 ... 12)","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3ebf45d76bd809bd41cc8d182a5d5287.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=166823&mlfb=3RV2411-0AA20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0AA20/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2411-0AA20 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3RV2411-0AA20's listed depth?","answer":"The depth is 97 mm, with a width of 45 mm and height of 106 mm."},{"question":"Will 3RV2411-0AA20 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both are Size S00 circuit breakers on the same 35 mm DIN rail footprint, so the mechanical fit and rail mounting are identical. However, 3RV2411-0AA20 is designed for transformer protection with a different trip curve and breaking capacity than the 3RV1011-0GA10; verify the protection coordination and terminal wiring before swapping."},{"question":"What compliance documentation does Siemens provide for 3RV2411-0AA20?","answer":"As a standard Siemens SIRIUS industrial control product, this circuit breaker is designed to meet applicable IEC and UL standards for circuit breakers. Specific compliance certificates (RoHS, REACH, UL, IEC) are available in the Siemens Industry Online Support documentation package for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0AA20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0AA20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}