{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0BA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0BA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0BA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0BA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker 3RV2411-0BA10, size S00, for transformer protection, 100 kA breaking capacity at 400 V AC, Class 10 trip, screw terminals.","salesMarkdown":"## Transformer protection breaker, S00 frame The Siemens 3RV2411-0BA10 is a SIRIUS circuit breaker purpose-designed for transformer protection, in the compact S00 frame size. It delivers 100 kA breaking capacity at 400 V AC, which means it can safely interrupt a fault current up to that level without cascading upstream — critical for transformer secondary-side protection where inrush and short-circuit currents can be severe. Trip Class 10 means the breaker will trip within 10 seconds at 7.2× the thermal setting, a standard match for transformer magnetizing inrush without nuisance tripping. Phase failure detection is built in, so a lost phase on the primary side will not leave the secondary energized in a single-phase condition. ## Mounting and panel integration Mounts via screw fixing or snap-on onto 35 mm DIN rail per DIN EN 60715. The S00 footprint — 45 mm wide, 97 mm deep — fits standard distribution panels and leaves room for adjacent breakers or contactors in a motor control center row. Any mounting position is permitted, which simplifies layout in tight enclosures. Clearance requirements: 50 mm above and below, 30 mm to the sides, zero forward or backward. This keeps heat dissipation and arc-fault venting within the manufacturer's design envelope.","metaTitle":"Siemens 3RV2411-0BA10 SIRIUS Circuit Breaker, Transformer Pr","metaDescription":"Siemens 3RV2411-0BA10 SIRIUS circuit breaker for transformer protection, size S00, 100 kA breaking capacity at 400 V, Class 10 trip, current production. Available to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2411-0BA10","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for transformer protection A-release 0.14...0.2 A N-release 4.2 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.2 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.2 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.2 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.2 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"4.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.14 ... 0.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$36.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95ff298fa42dd22acdb4aed72b6d2dec.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=119715&mlfb=3RV2411-0BA10"},"ai":{"faq":[{"question":"What is 3RV2411-0BA10's listed depth (97 mm) on this component line?","answer":"The depth is 97 mm. Combined with a width of 45 mm and height of 97 mm, the S00 footprint fits standard DIN-rail enclosures."},{"question":"Will 3RV2411-0BA10 drop into a panel that was specified around 3RV2011-0AA10 without rewiring?","answer":"Both are S00 frame breakers with the same 45 mm width and screw-terminal main contacts (M3), so the mechanical fit and terminal spacing are identical. The 3RV2411-0BA10 is specifically designed for transformer protection, while the 3RV2011-0AA10 is a general motor-protection variant — verify the trip curve and phase-failure logic match your application before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0BA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0BA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}