{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0CA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0CA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0CA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0CA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-0CA10, Size S00, for transformer protection, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Transformer-protection breaker, Size S00 Any mounting position works. That 45 mm width is the critical panel-density number: it occupies one standard 45 mm module slot, so a 12-way panel row holds 12 of these breakers. Accepts 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². Screwdriver shaft diameter 5 to 6 mm, Pozidriv size 2 tip. Main contact screws are M3. No ground-fault detection built in; phase-failure detection is included. ## Environmental and ratings Rated voltage 20 to 690 V. Maximum switching frequency in AC-3 duty is 15 operations per hour. The 100 kA breaking capacity repeats across 240 V, 400 V, 500 V, and 690 V AC — so it holds its interrupting rating across the full low-voltage range, not just at one voltage point.","metaTitle":"Siemens 3RV2411-0CA10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2411-0CA10 SIRIUS circuit breaker for transformer protection. Size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC. Available to order — RFQ for current pricing","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.25 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.25 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.25 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.25 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.25 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"5.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.18 ... 0.25 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=336789&mlfb=3RV2411-0CA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0CA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RV2411-0CA10?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What is the closest functional alternative to the 3RV2411-0CA10?","answer":"The 3RV2011-0AA10 is the closest functional peer within the SIRIUS range — same Size S00 frame and Trip Class 10, but it is a general motor-protection breaker, not transformer-protection-specific. The 3RV2411-0CA10's 100 kA breaking capacity at 400 V is higher than the 3RV2011-0AA10's typical 55 kA at 400 V, so the 3RV2411-0CA10 is the correct choice where higher interrupting capacity is specified for transformer duty."},{"question":"Does the 3RV2411-0CA10 drop into a panel built for the 3RV2011-0AA10?","answer":"Yes — both are Size S00, same 45 mm width and DIN-rail snap-on mounting per DIN EN 60715. Terminal type and wire range are identical (screw-type, 0.75–4 mm²). No rewiring needed for the same footprint."},{"question":"What compliance documentation is available for the 3RV2411-0CA10?","answer":"The SIRIUS series carries UL, CSA, CE, and IEC certifications standard for the product line. RoHS and REACH declarations are available from Siemens documentation. Specific certificate numbers for this order code are confirmed at order time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0CA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0CA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}