{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0EA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0EA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0EA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0EA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-0EA15, for transformer protection, 100 kA breaking capacity at 400 V AC, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker with 100 kA interrupting capacity The Siemens 3RV2411-0EA15 is a SIRIUS-brand circuit breaker designed specifically for transformer protection, not general motor or feeder duty. Its 100 kA breaking capacity at 400 V AC means it can safely interrupt fault currents up to that level without upstream fuses — a key spec for panel selectivity studies where the transformer inrush and secondary-side fault current must be coordinated. Trip Class 10 defines the maximum trip time at 7.2× rated current: 10 seconds. For a transformer primary protector, that thermal curve is sized to ride through magnetizing inrush without nuisance tripping while still clearing a sustained overload. Phase failure detection is built in, so a lost phase on the secondary side will trip the primary breaker — a feature not universal on basic MCPs. ## Mounting and wiring Mounts via screw and snap-on onto 35 mm standard mounting rail per DIN EN 60715. The 45 mm width is a standard 2-module footprint on that rail. Screw-type terminals on the main circuit accept 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²) — strip length per the manufacturer's torque spec, not guessed. Any mounting position is permitted, which simplifies panel layout when the transformer is in a tight enclosure.","metaTitle":"Siemens 3RV2411-0EA15 SIRIUS Circuit Breaker, 100 kA, Transf","metaDescription":"Siemens 3RV2411-0EA15 SIRIUS circuit breaker for transformer protection. 100 kA breaking capacity at 400 V AC, Trip Class 10, phase failure detection. Available to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2411-0EA15","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for transformer protection A-release 0.28...0.4 A N-release 8.2 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.4 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.4 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.4 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.4 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"8.2 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.28 ... 0.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7206932825c78fc485371e6194b797ce.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=210595&mlfb=3RV2411-0EA15"},"ai":{"faq":[{"question":"Where can I buy 3RV2411-0EA15 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is the breaking capacity of 3RV2411-0EA15?","answer":"100 kA at 240 V AC, 400 V AC, 500 V AC, and 690 V AC. That interrupting rating holds across the common industrial voltage levels, so it coordinates with most downstream transformer secondary protection without requiring a current-limiting upstream device."},{"question":"Does 3RV2411-0EA15 include phase failure detection?","answer":"Yes, phase failure detection is built in. If one phase is lost on the secondary side, the breaker will trip — this is a standard feature on the transformer-protection variant and is not available on all SIRIUS breaker versions."},{"question":"What compliance documentation does Siemens provide for 3RV2411-0EA15?","answer":"As a SIRIUS product, Siemens provides a declaration of conformity covering the applicable EU directives (Low Voltage Directive, EMC Directive), plus RoHS and REACH compliance statements. The product carries CE marking and is designed to meet UL and IEC standards per the manufacturer's documentation package."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0EA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0EA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}