{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0GA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0GA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0GA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0GA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, circuit breaker for transformer protection, size S00, 45 mm width, 100 kA breaking capacity at 400 V AC, Trip Class 10, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker, size S00 The 100 kA breaking capacity holds at 240 V, 400 V, 500 V, and 690 V AC — a flat curve that simplifies selectivity studies. At 690 V the gL/gG fuse backup is 6 A, which is the fuse rating, not the breaker's own interrupting rating. For a transformer secondary fault, the breaker's own 100 kA at 400 V covers most industrial service-entrance scenarios without an upstream fuse. ## Panel integration and clearances Depth is 97 mm, matching the S00 frame height. Side clearance required is 30 mm; top and bottom each need 50 mm. Zero clearance forward and backward — the breaker can sit flush against a gland plate or back panel. Screw-type terminals on the main circuit accept 2× (0.75 to 2.5 mm²) solid or stranded, or 2× 4 mm². The screwdriver shaft diameter is 5 to 6 mm, and the main contact screws are M3.","metaTitle":"Siemens 3RV2411-0GA10 SIRIUS Circuit Breaker, 100 kA, Class","metaDescription":"Siemens 3RV2411-0GA10 SIRIUS transformer-protection circuit breaker, size S00. 100 kA breaking capacity at 400 V AC, Trip Class 10. 45 mm wide, DIN rail mount. Sourced to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.63 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.63 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"0.63 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"0.63 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.63 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=369497&mlfb=3RV2411-0GA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0GA10/alternatives.json"},"ai":{"faq":[{"question":"Is 3RV2411-0GA10 available via RFQ confirmation and what is the lead time?","answer":"Availability and current pricing are confirmed at quote time. Submit an RFQ for this order code and we will source it through our supply channels."},{"question":"What is 3RV2411-0GA10's listed depth?","answer":"The depth is 97 mm, matching the S00 frame height. Side clearance is 30 mm; top and bottom each need 50 mm."},{"question":"What is 3RV2411-0GA10's listed width?","answer":"The width is 45 mm, which occupies three 15 mm module spaces on a 35 mm DIN rail."},{"question":"Will 3RV2411-0GA10 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both are size S00 with the same 45 mm width and 97 mm depth, so the physical footprint and terminal layout are identical. The main difference is the protection curve — the 3RV2411-0GA10 is tuned for transformer inrush, while the 3RV1011-0GA10 is a general-purpose motor-protective breaker. Rewiring is not required, but the protection settings must be reviewed."},{"question":"What compliance documentation does Siemens provide for 3RV2411-0GA10?","answer":"Standard SIRIUS documentation includes RoHS, REACH, UL, and IEC declarations. These are available from Siemens upon request or through the product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0GA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0GA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}