{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0HA20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0HA20","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0HA20","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0HA20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, Size S00, for transformer protection, 3RV2411-0HA20, 100 kA breaking capacity at 400 V, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker in the SIRIUS S00 frame Rated breaking capacity hits 100 kA at 240 V, 400 V, 500 V, and 690 V AC — that is full-range fault clearance without cascading upstream, a real advantage when coordinating selectivity in a transformer secondary circuit. ## Panel integration — DIN rail footprint and clearances Clearance requirements: 50 mm above and below, 30 mm to the side, zero forward or backward. That zero forward clearance means the breaker can sit flush against a gland plate or back panel without derating. Screwdriver shaft diameter is 3 mm, tip size 3.0 × 0.5 mm — standard Pozidriv or slotted, no special tooling needed on the line. Storage and transport handle -50 to +80 °C. The rated voltage range is 20 to 690 V, covering low-voltage control transformers up to 690 V secondary. Maximum switching frequency in AC-3 duty is 15 operations per hour — adequate for a transformer primary disconnect that cycles infrequently, not for a motor-starting application needing frequent inrush.","metaTitle":"Siemens 3RV2411-0HA20 SIRIUS Circuit Breaker, 100 kA, Class","metaDescription":"Siemens 3RV2411-0HA20 SIRIUS circuit breaker for transformer protection. Size S00, 100 kA breaking capacity at 400 V, Trip Class 10, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","at 690 V":"gL/gG 6 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"0.8 A","at 500 V rated value":"100 kA","at 600 V rated value":"0.8 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"0.8 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.8 A","at AWG cables for main contacts":"2x (20 ... 12)","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"16 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/01f158bf2d594154d1e23de81a7e5c59.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=90031&mlfb=3RV2411-0HA20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0HA20/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV2411-0HA20 drop into a panel specified around 3RV1011-0GA10 without rewiring?","answer":"Both are Size S00 breakers on the same 35 mm DIN rail footprint, so the mechanical fit and rail spacing are identical. The terminal type and wire range should be verified against the existing panel's wiring — the 3RV2411 uses spring-loaded terminals, while the 3RV1011-0GA10 may differ. No rewiring of the rail or enclosure is needed."},{"question":"What is 3RV2411-0HA20's listed depth?","answer":"97 mm. Combined with the 45 mm width and 106 mm height, it fits the standard S00 envelope."},{"question":"What compliance documentation does this brand provide for 3RV2411-0HA20?","answer":"The manufacturer provides standard documentation for the SIRIUS series including RoHS and REACH declarations, and the product carries IEC and UL certifications typical for this class. Specific document numbers are available on request with an RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0HA20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0HA20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}