{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-0JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-0JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-0JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2411-0JA10 circuit breaker, for transformer protection, 100 kA breaking capacity at 400 V AC, Trip Class 10, screw-type terminals, 45 mm width, DIN rail mount.","salesMarkdown":"It snaps onto a 35 mm DIN rail per DIN EN 60715 and fits a standard 45 mm wide slot in the panel — a tight fit for a 100 kA rated device at 400 V. Rated breaking capacity hits 100 kA at 240 V, 400 V, 500 V, and 690 V AC, so it clears high-fault transformer secondaries without cascading upstream. The Trip Class 10 thermal curve matches transformer inrush — it holds through magnetizing current without nuisance tripping, then opens on sustained overload. ## Mounting and spacing Main terminals accept up to 2x 4 mm² stranded or 2x 2.5 mm² solid. At 97 mm deep by 45 mm wide by 97 mm tall, it occupies roughly the same footprint as a motor-protective breaker but is tuned for transformer duty. Rated operational voltage spans 20 to 690 V, covering most low-voltage transformer primaries and secondaries. At 230 V it switches 0.2 kW loads; at 575/600 V it is rated 0.5 hp. No ground-fault detection on this variant; that is a separate SIRIUS family option. Maximum mechanical switching frequency is 15 operations per hour in AC-3 and AC-3e duty — not a high-cycle device.","metaTitle":"Siemens 3RV2411-0JA10 SIRIUS Circuit Breaker, 100 kA, Transf","metaDescription":"Siemens 3RV2411-0JA10 SIRIUS circuit breaker for transformer protection. 100 kA breaking capacity at 400 V, Trip Class 10, 45 mm wide, DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 500 V":"gL/gG 10 A","at 690 V":"gL/gG 10 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"1 A","at 500 V rated value":"100 kA","at 600 V rated value":"1 A","at 690 V rated value":"100 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 575/600 V rated value":"0.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$36.83","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e8f2845714b35c73ff2525f5947cb023.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=309023&mlfb=3RV2411-0JA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-0JA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2411-0JA10 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through our distribution network. Submit a request for current pricing and availability — we confirm both at quote time."},{"question":"Will 3RV2411-0JA10 drop into a panel specified around 3RV2011-0AA10 without rewiring?","answer":"The 3RV2411-0JA10 shares the same 45 mm width and DIN-rail mounting as the 3RV2011 series, so it fits the same panel slot. However, the 3RV2411 is a transformer-protection breaker with a different thermal curve (Trip Class 10) and 100 kA breaking capacity, while the 3RV2011 is a motor-protective breaker — verify the application before swapping, as the overload characteristics differ."},{"question":"What is 3RV2411-0JA10's listed depth?","answer":"The depth is 97 mm, with a width of 45 mm and height of 97 mm. Clearance required: 50 mm above and below, 30 mm to the sides, zero forward or backward."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-0JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-0JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}