{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1AA20","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1AA20","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1AA20","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1AA20","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-1AA20, for transformer protection, 100 kA breaking capacity at 400 V, Class 10 trip, phase failure detection, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"It's not a general-purpose motor protection breaker — the design tailors the trip curve to handle transformer inrush without nuisance tripping, while still providing short-circuit and overload protection for the primary side. Rated operating voltage spans 20 to 690 V. The breaking capacity sits at 100 kA at 400 V and holds that same 100 kA at 240 V, 500 V, and 690 V — that's a flat high-fault rating across the common industrial voltages, meaning you don't have to derate for higher-voltage panels. That's standard for motor circuits, but here it's applied to transformer primary protection — the fast trip still allows for the magnetizing inrush on energization. Any mounting position is acceptable — horizontal, vertical, upside-down, doesn't matter for the thermal-magnetic trip. That's tight enough for dense panels. Dimensions: 45 mm wide, 106 mm tall, 97 mm deep. Main circuit connections use spring-loaded terminals — no screwdriver needed for the power wiring, just strip and push. ## Environmental and operating limits That's a wide storage range — fine for unheated warehouses or truck beds in winter. Maximum switching frequency at AC-3 duty: 15 operations per hour. That's not a high-cycling device — don't spec it for frequent switching applications like welding or rapid-start conveyors. It's meant for transformer primary protection where switching is infrequent.","metaTitle":"Siemens 3RV2411-1AA20 SIRIUS Circuit Breaker, Transformer Pr","metaDescription":"Siemens 3RV2411-1AA20 SIRIUS circuit breaker for transformer protection. 100 kA breaking capacity at 400 V, Class 10 trip, phase failure detection. Current production. Available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ba9968b09008a6a4f342806c2c7c776d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=15405&mlfb=3RV2411-1AA20","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1AA20/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1AA20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1AA20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}