{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1CA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1CA15","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1CA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1CA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2411-1CA15, circuit breaker for transformer protection, Trip Class 10, 45 mm width, 100 kA breaking capacity at 400 V, phase failure detection, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## Transformer-protection breaker with Trip Class 10 ## Breaking capacity and fuse coordination Rated breaking capacity hits 100 kA at 400 V and 500 V, dropping to 10 kA at 690 V. For fuse backup coordination, the spec calls for gL/gG fuses: 25 A up to 500 V, 20 A at 690 V. If you're coordinating with a downstream contactor for motor starting, note the maximum operating rate of 15 switching cycles per hour in AC-3 duty. The 45 mm width (three TE) is standard for SIRIUS breakers — fits alongside contactors and overloads in a motor control center row. That matters when packing multiple breakers in a row — you can butt them front-to-back but need breathing space top and bottom for arc venting and heat rise. ## Environmental and wiring specs That -20 °C floor means it's fine for unheated electrical rooms in temperate climates but not for outdoor enclosures in deep freeze. Main contact terminals accept M3 screws; wire range is 2× (0.5 to 1.5 mm²) solid or stranded, or 2× (0.75 to 2.5 mm²).","metaTitle":"Siemens 3RV2411-1CA15 SIRIUS Circuit Breaker, Transformer Pr","metaDescription":"Siemens 3RV2411-1CA15 SIRIUS circuit breaker for transformer protection. Trip Class 10, 100 kA breaking at 400 V, phase failure detection, DIN rail mount. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2411-1CA15","Height":"97 mm","Upwards":"50 mm","at 24 V":"1 A","at 60 V":"0.15 A","Forwards":"0 mm","at 120 V":"0.5 A","at 125 V":"0.5 A","at 230 V":"0.5 A","at 400 V":"gL/gG 25 A","at 500 V":"gL/gG 25 A","at 690 V":"gL/gG 20 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for transformer protection A-release 1.8...2.5 A N release 52 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.17 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"2.5 A","at 500 V rated value":"100 kA","at 600 V rated value":"2.5 A","at 690 V rated value":"10 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 200/208 V rated value":"0.5 hp","at 220/230 V rated value":"0.5 hp","at 460/480 V rated value":"1 hp","at 575/600 V rated value":"1.5 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"2.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"2.5 A","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Of The Auxiliary And Control Contacts":"M3","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"1","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","contact rating of auxiliary contacts according to UL":"C300 / R300","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","For Short-Circuit Protection Of The Auxiliary Switch Required":"Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"52 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.8 ... 2.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ce764963e79e9a7180cf509f4c5c2959.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=434571&mlfb=3RV2411-1CA15"},"ai":{"faq":[{"question":"What is the breaking capacity of 3RV2411-1CA15 at 400 V?","answer":"Rated breaking capacity is 100 kA at 400 V, which means it can safely interrupt faults up to that level without needing upstream devices to clear."},{"question":"Will 3RV2411-1CA15 drop into a panel specified for 3RV1011-0GA10?","answer":"Both mount on 35 mm DIN rail per DIN EN 60715 and share the SIRIUS form factor, so the physical fit is the same. However, the 3RV2411-1CA15 is designed for transformer protection (Trip Class 10) while the 3RV1011-0GA10 is a motor-protective breaker — verify the trip curve matches your load before swapping."},{"question":"How do I get current pricing and availability for 3RV2411-1CA15?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1CA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1CA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}