{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1DA20-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1DA20-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1DA20-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1DA20-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-1DA20-0DA0, Size S00, for transformer protection, Trip Class 10, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker, Size S00 Rated breaking capacity reaches 100 kA at 240 V AC, 400 V AC, and 500 V AC, dropping to 10 kA at 690 V AC. At 400 V the unit is rated to clear a 25 A gG fuse-limit; at 500 V that rises to 32 A gG, and at 690 V it returns to 25 A gG. Mounting position is any, which simplifies panel layout. Required clearance: 50 mm upwards, 50 mm downwards, 30 mm at the sides, and zero forwards or backwards — so it can sit flush against a backplate or enclosure wall. The 45 mm width and 97 mm depth fit standard S00 footprint, meaning a panel originally laid out for a 3RV2011-0BA20 or 3RV2021-1FA15 accepts this unit without re-drilling the DIN rail or re-routing wiring, provided the terminal scheme (spring-loaded terminals for the main current circuit) matches the existing lug arrangement. The lifecycle stage is listed as current — this is an active, in-production catalog number within the SIRIUS family. No end-of-life notification or last-time-buy date is available.","metaTitle":"Siemens 3RV2411-1DA20-0DA0 SIRIUS Circuit Breaker, Size S00,","metaDescription":"Siemens 3RV2411-1DA20-0DA0 SIRIUS circuit breaker for transformer protection, Size S00, Trip Class 10, 100 kA breaking capacity at 400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2411-1DA20-0DA0","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gG 25 A","at 500 V":"gG 32 A","at 690 V":"gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"circuit breaker size S00 for transformer protection without phase failure protection A-release 2.2...3.2 A short-circuit release 65 A spring-loaded terminal standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.6 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"10 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"spring-loaded terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"3.2 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"3.2 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"3.2 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"2.2 ... 3.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f1d87f2824a4426852614eb6f5269f4b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1497487&mlfb=3RV2411-1DA20-0DA0"},"ai":{"faq":[{"question":"Will 3RV2411-1DA20-0DA0 replace 3RV2011-0BA20 without rewiring?","answer":"Both are Size S00 breakers on the same 45 mm DIN-rail footprint, so the mechanical fit is identical. However, the 3RV2411-1DA20-0DA0 uses spring-loaded terminals for the main circuit, while the 3RV2011-0BA20 may use screw terminals — verify the terminal type on the existing panel before assuming a direct swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1DA20-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1DA20-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}