{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1EA20-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1EA20-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1EA20-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1EA20-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2411-1EA20-0DA0, circuit breaker for transformer protection, size S00, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The Siemens 3RV2411-1EA20-0DA0 is a SIRIUS circuit breaker specifically designed for transformer protection, size S00. The CLASS 10 trip class means it will hold through a transformer inrush and still trip on a hard fault — that's the right curve for a dry-type or small cast-coil unit feeding a control panel. ## Breaking capacity and backup protection Rated breaking capacity hits 100 kA at 240 V, 400 V, and 500 V AC; at 690 V it drops to 6 kA AC. For backup protection, the manufacturer specifies gG fuse ratings: 32 A at 400 V and 500 V, 25 A at 690 V. If you're coordinating with an upstream fuse, those are the maximums the breaker relies on for its rated short-circuit performance. Mounting position is any, which simplifies panel layout. Required clearances: 50 mm above and below, 30 mm to the side, zero forward or backward.","metaTitle":"Siemens 3RV2411-1EA20-0DA0 SIRIUS Circuit Breaker, S00, CLAS","metaDescription":"Siemens 3RV2411-1EA20-0DA0 SIRIUS circuit breaker, size S00, CLASS 10 trip, 100 kA breaking capacity at 400 V AC. Transformer protection design. Current production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gG 32 A","at 500 V":"gG 32 A","at 690 V":"gG 25 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,5 ... 4 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.8 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"4 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"spring-loaded terminals","Temperature Compensation":"-20 ... +60 °C","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 3 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"3,0 x 0,5 mm","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"4 A","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"4 A","Design Of The Short-Circuit Trip":"magnetic","Between Main And Auxiliary Circuit":"400 V","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","Finely Stranded Without Core End Processing":"2x (0.5 ... 2.5 mm²)","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms Sinus","Electrical Endurance (Switching Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"82 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"No","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1497488&mlfb=3RV2411-1EA20-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1EA20-0DA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV2411-1EA20-0DA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the breaking capacity of 3RV2411-1EA20-0DA0 at 400 V?","answer":"Rated breaking capacity is 100 kA at 400 V AC. At 690 V AC it is 6 kA."},{"question":"What trip class does this circuit breaker have?","answer":"Trip class is CLASS 10, meaning it will hold through transformer inrush current and still trip on a sustained overload within 10 seconds at 7.2× the thermal setting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1EA20-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1EA20-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}