{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1FA20-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1FA20-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1FA20-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1FA20-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-1FA20-0DA0, for transformer protection, size S00, Class 10 trip, 1.1 kW at 230 V, 100 kA breaking capacity at 400 V, spring-loaded terminals.","salesMarkdown":"The Siemens SIRIUS 3RV2411-1FA20-0DA0 is a circuit breaker specifically designed for transformer protection, size S00. It's a current-production item, so no lifecycle concerns for a new BOM line. Rated at 1.1 kW at 230 V, it provides a Class 10 trip characteristic, meaning it will hold through motor inrush but trip quickly on a sustained overload — standard for protecting the transformer primary winding against secondary-side faults. Any mounting position is allowed. No need for ferrules, though they help on stranded — strip length is standard for the cage. That's tight enough for most DIN-rail layouts, but watch the upward gap if you're stacking breakers. The Class 10 trip curve is the key selection parameter here — it allows up to 10 seconds at 7.2x rated current before tripping, which covers transformer magnetizing inrush without nuisance trips. If your transformer has a higher inrush or you need coordination with downstream breakers, check the time-current curve. The back-up fuse recommendation is gG 32 A at 400 V or 500 V, stepping down to gG 25 A at 690 V — size the upstream fuse accordingly. No derating needed in most ventilated enclosures, but if it's in a sealed box next to a transformer, watch the ambient. No ground fault or phase failure detection built in — this is a straight thermal-magnetic breaker. If you need those functions, you'd add a separate relay or move to a motor-protective circuit breaker variant.","metaTitle":"Siemens SIRIUS 3RV2411-1FA20-0DA0 Circuit Breaker, 1.1 kW at","metaDescription":"Siemens SIRIUS 3RV2411-1FA20-0DA0 circuit breaker for transformer protection. 1.1 kW at 230 V, Class 10 trip, 100 kA breaking capacity at 400 V. Size S00, spring-loaded terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"106 mm","Trip Class":"CLASS 10","Product Status":"Active","Temp Operating Max":"60 °C","Temp Operating Min":"-20 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/211f4c4920a517dadba5f10b2a534bdc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1497489&mlfb=3RV2411-1FA20-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1FA20-0DA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1FA20-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1FA20-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}