{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2411-1JA10 circuit breaker for transformer protection, 100 kA SCCR at 400 V, Trip Class 10, screw-type terminals, 45 mm width, 97 mm depth.","salesMarkdown":"That means its overload curve and short-circuit release are tuned to handle transformer inrush without nuisance tripping — a detail that matters when you're protecting a dry-type or distribution transformer on a 400 V bus. At 690 V it still clears 4 kA. That SCCR lets this breaker sit upstream of smaller branch devices without worrying about cascading failure during a bolted fault. If your transformer secondary feeds an ungrounded delta or you need GF protection, you'll add an external ground-fault relay or specify a different variant. ## Termination & Environment Main current circuit connections use screw-type terminals, accepting 2× (0.75 to 2.5 mm²) solid or stranded, or 2× 4 mm². The M3 screw is standard for this frame size; torque to the Siemens spec during panel build. That covers most indoor panel environments — no special derating needed for a typical MCC room or cabinet. The fuse backup requirements are specified: gL/gG 50 A at 400 V, 40 A at 500 V, and 40 A at 690 V — coordinate your upstream fuse selection accordingly.","metaTitle":"Siemens 3RV2411-1JA10 SIRIUS Circuit Breaker, Transformer Pr","metaDescription":"Siemens 3RV2411-1JA10 SIRIUS circuit breaker for transformer protection. 100 kA SCCR at 400 V, Trip Class 10, screw terminals. Current production — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gL/gG 50 A","at 500 V":"gL/gG 40 A","at 690 V":"gL/gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1.5 hp","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 480 V rated value":"10 A","at 500 V rated value":"42 kA","at 600 V rated value":"10 A","at 690 V rated value":"4 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at 110/120 V rated value":"0.5 hp","at 200/208 V rated value":"2 hp","at 220/230 V rated value":"3 hp","at 460/480 V rated value":"5 hp","at 575/600 V rated value":"10 hp","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"10 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"10 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","at AWG cables for main contacts":"2x (18 ... 14), 2x 12","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","with high demand rate according to SN 31920":"50 %","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"100 000","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/052ad32f4da89d446d7197d57c2e20f7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=137426&mlfb=3RV2411-1JA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1JA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3RV2411-1JA10?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"Does the 3RV2411-1JA10 include ground fault detection?","answer":"No — ground fault detection is not fitted. Phase failure detection is included. If ground fault protection is required, an external relay or a different 3RV variant must be specified."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}