{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-1JA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-1JA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-1JA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1JA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV2411-1JA10-0BA0, Size S00, Trip Class 10, for transformer protection, 45 mm width, screw and snap-on DIN rail mounting.","salesMarkdown":"The interrupting ratings tell you where this breaker can safely clear a fault: 100 kA at 230 V and 400 V AC, 42 kA at 500 V AC, and 4 kA at 690 V AC. Ground fault detection is not included, so if that's required, plan for an external GF module. ## Integration notes — wiring and clearances Screw-type terminals on the main current circuit accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm². The screwdriver shaft should be 5 to 6 mm diameter, Pozidriv size 2 tip. Clearance requirements: 50 mm upwards and downwards, 30 mm at the sides, zero forwards and backwards — so it can sit flush against the back panel. The gG fuse backup ratings at 400 V (50 A), 500 V (40 A), and 690 V (40 A) should be matched when coordinating with upstream protection.","metaTitle":"Siemens 3RV2411-1JA10-0BA0 SIRIUS Circuit Breaker, Trip Clas","metaDescription":"Siemens SIRIUS 3RV2411-1JA10-0BA0 circuit breaker for transformer protection. 100kA SCCR at 400V, Trip Class 10, 45mm wide. Screw and snap-on DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 400 V":"gG 50 A","at 500 V":"gG 40 A","at 690 V":"gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-50 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"2.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"42 kA","at 690 V rated value":"4 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"42 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"500","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"10 A","Of Auxiliary Contacts Typical":"500","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"500","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2d5c10aba861019538c02d48ca5de3df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=275592&mlfb=3RV2411-1JA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-1JA10-0BA0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV2411-1JA10-0BA0?","answer":"The 3RV2023-4DA10 is a Size S00 circuit breaker from the same SIRIUS family, but it is designed for standard motor protection rather than transformer protection. The 3RV2411-1JA10-0BA0 has a specific thermal curve tuned for transformer inrush, so direct substitution without verifying the trip characteristic against your transformer's inrush profile is not recommended."},{"question":"Where can I buy 3RV2411-1JA10-0BA0?","answer":"This part is sourced to order through independent distribution channels. Submit an RFQ to confirm current availability and pricing — the quote will reflect real-time market conditions."},{"question":"What compliance documentation does this brand provide for 3RV2411-1JA10-0BA0?","answer":"As a Siemens SIRIUS product, it carries the standard CE marking for the European market and is designed to meet IEC/EN 60947-2 and 60947-4-1 requirements. RoHS and REACH compliance documentation is typically available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-1JA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-1JA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}