{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2411-4AA10-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2411-4AA10-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3RV2411-4AA10-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2411-4AA10-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker for transformer protection, 3RV2411-4AA10-0BA0, S00 frame, Trip Class 10, 45 mm wide, breaking capacity 100 kA at 240 V AC.","salesMarkdown":"Rated breaking capacity at 240 V AC is 100 kA, dropping to 30 kA at 400 V AC, 5 kA at 500 V AC, and 2 kA at 690 V AC. For AC-side faults, the figures are 100 kA at 240 V AC, 55 kA at 400 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC. These numbers tell you where this breaker can sit in a distribution hierarchy: at 400 V it handles a 30 kA prospective fault current, which covers most industrial panelboards fed by a transformer of moderate size. At 690 V the 2 kA rating limits it to low-fault-current branches or downstream of a current-limiting device. Dimensions are 97 mm deep, 45 mm wide, 97 mm tall — the 45 mm width is a single modular unit, so it occupies one 45 mm slot on the rail. Clearance: 50 mm upward, 50 mm downward, 30 mm to the side, zero forward or backward. Any mounting position is allowed. The S00 frame size means it fits alongside other S00 accessories (auxiliary switches, shunt trips) on the same DIN rail without extra adapters. Main circuit terminals are screw-type, accepting 2× (0.75 to 2.5 mm²) solid or stranded, or 2× 4 mm². Screwdriver shaft diameter must be 5 to 6 mm. Terminal screws are M3. These are standard panel-building sizes — no special crimp tools needed, but the 4 mm² capacity means you can land a single larger conductor if you parallel the two ports. ## Environmental and operating limits The wide cold end (-50 °C) is unusual for a molded-case breaker — it means this part can live in an unheated enclosure in a cold climate without derating for low ambient. The rated insulation voltage is 20 to 690 V, covering standard low-voltage systems up to 690 V phase-to-phase.","metaTitle":"Siemens 3RV2411-4AA10-0BA0 SIRIUS Circuit Breaker, S00, Clas","metaDescription":"Siemens 3RV2411-4AA10-0BA0 SIRIUS circuit breaker for transformer protection, S00 frame, Trip Class 10, 45 mm wide, breaking capacity 100 kA at 240 V AC. Active production. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","at 240 V":"gG 80 A","at 400 V":"gG 63 A","at 500 V":"gG 50 A","at 690 V":"gG 40 A","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"20 ... 690 V","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-50 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","For Main Contacts":"M3","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"4 kW","at 240 V rated value":"100 kA","at 400 V rated value":"30 kA","at 500 V rated value":"5 kA","at 690 V rated value":"2 kA","Design Of The Product":"For transformer protection","Ground Fault Detection":"No","Phase Failure Detection":"Yes","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"55 kA","at AC at 500 V rated value":"10 kA","at AC at 690 V rated value":"4 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"500","at AC in hot operating state":"9.25 W","at AC-3 at 400 V rated value":"16 A","Of Auxiliary Contacts Typical":"500","Substance Prohibitance (Date)":"10/01/2009","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"3.1 W","With Side-By-Side Mounting At The Side":"0 mm","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"0","shock resistance according to IEC 60068-2-27":"25g / 11 ms","Electrical Endurance (Operating Cycles) Typical":"500","Size Of Contactor Can Be Combined Company-Specific":"S00, S0","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"286 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3fd93593c8a29d17fd689f9b5b1304af.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=276453&mlfb=3RV2411-4AA10-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2411-4AA10-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV2411-4AA10-0BA0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 3RV2411-4AA10-0BA0's listed depth?","answer":"The depth is 97 mm, width 45 mm, height 97 mm — a single 45 mm DIN-rail slot."},{"question":"Will 3RV2411-4AA10-0BA0 drop into a panel specified around 3RV1011-1HA10 without rewiring?","answer":"Both are S00 frame circuit breakers on 35 mm DIN rail, so the mechanical footprint is the same. Terminal sizes and wiring capacities differ — verify the conductor cross-section against the 3RV2411's terminal specs (2× 0.75–2.5 mm² or 2× 4 mm²) before assuming a drop-in swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2411-4AA10-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2411-4AA10-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}