{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2711-0JD10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2711-0JD10","canonicalUrl":"https://aoctrl.com/siemens/3RV2711-0JD10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2711-0JD10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2711-0JD10 circuit breaker, size S00, 100 kA interrupting capacity at 240-690 V AC, screw and snap-on 35 mm DIN rail mount, UL 489 system protection design.","salesMarkdown":"The Siemens SIRIUS 3RV2711-0JD10 is a circuit breaker in the S00 frame size, designed for system protection per UL 489 and CSA C22.2 No. 5. It's the part that sits upstream of a motor starter or downstream of a feeder breaker, providing short-circuit and overload protection for the branch circuit. Any mounting position is permitted, which simplifies layout when the panel is tight on vertical clearance. That last one means you can butt it against a panel door or cover without derating. Rated operational voltage spans 20 to 690 V AC. The 100 kA interrupting capacity holds across the full range — 240 V, 400 V, 500 V, 690 V — which is unusual; many breakers derate at higher voltages. That flat SCCR curve simplifies coordination studies: one number for the whole voltage band. Maximum switching frequency under AC-3 duty (motor starting) is 15 operations per hour — fine for a pump or conveyor start cycle, not for a rapid-reversing application.","metaTitle":"Siemens 3RV2711-0JD10 SIRIUS Circuit Breaker, S00, 100 kA SC","metaDescription":"Siemens SIRIUS 3RV2711-0JD10 circuit breaker, size S00, 100 kA interrupting capacity at 240-690 V AC. UL 489 system protection. DIN-rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2711-0JD10","Height":"144 mm","Upwards":"70 mm","Forwards":"0 mm","at 500 V":"gG 10 A","at 690 V":"gG 10 A","Backwards":"0 mm","Downwards":"70 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 1 A N-release 13 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"1 ... 10 mm², max. 2x 10 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.2 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"100 kA","Design Of The Product":"For system protection according to UL 489/CSA C22.2 No. 5","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"100 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"5.5 W","at AC-3 at 400 V rated value":"1 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"1 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (14 ... 10)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"1.8 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"1 ... 16 mm², max. 6 + 16 mm²","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2.5 ... 3 N·m","with high demand rate according to SN 31920":"50 %","shock resistance according to IEC 60068-2-27":"25 g / 11 ms (rectangular impulse and sine pulse)","Electrical Endurance (Operating Cycles) Typical":"100 000","at 480 AC Y/277 V according to UL 489 rated value":"65 kA","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$69.85","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a50027d0daa8667c996bcda929b6ed98.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=323110&mlfb=3RV2711-0JD10"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3RV2711-0JD10?","answer":"100 kA at 240 V through 690 V AC — the rating holds flat across the entire voltage range, which is a strong coordination advantage."},{"question":"What are the mounting dimensions for 3RV2711-0JD10?","answer":"45 mm wide, 144 mm tall, 97 mm deep. Mounts on 35 mm DIN rail via screw and snap-on. Requires 70 mm clearance above and below, 30 mm to the side, zero forward clearance."},{"question":"Will 3RV2711-0JD10 drop into a panel designed for 3RV2011-0AA10?","answer":"Both are S00 frame size on 35 mm DIN rail, so the mechanical footprint and mounting are identical. The difference is in the interrupting rating and protection curve — verify coordination before swapping."},{"question":"Where can I buy 3RV2711-0JD10 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2711-0JD10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2711-0JD10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}