{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2711-1CD10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2711-1CD10","canonicalUrl":"https://aoctrl.com/siemens/3RV2711-1CD10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2711-1CD10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, circuit breaker, 3RV2711-1CD10, S00 frame, 100 kA at 400 V AC, screw and snap-on 35 mm DIN rail.","salesMarkdown":"The Siemens 3RV2711-1CD10 is a SIRIUS S00 circuit breaker for system protection, designed per UL 489 and CSA C22.2 No. 5. It mounts on 35 mm DIN rail (DIN EN 60715) via screw or snap-on — the S00 frame keeps the width at 45 mm, so it fits standard 45 mm-per-pole spacing in a motor control center or distribution panel. Rated operating voltage spans 20 to 690 V. The interrupting ratings are the headline: 100 kA at 240 V, 400 V, and 500 V AC; 10 kA at 690 V AC. Dimensions: 45 mm wide, 144 mm tall, 97 mm deep. That 97 mm depth is the body plus terminals — check gland-plate clearance if the panel is shallow, but the zero forward clearance means it doesn't protrude past the DIN rail front edge. Terminals are M4 screw-type for the main circuit, accepting 1 to 10 mm² solid/stranded, up to 2×10 mm². Screwdriver spec: Pozidriv #2, shaft diameter 5–6 mm. Mounting position any — no derating for horizontal or inverted install.","metaTitle":"Siemens 3RV2711-1CD10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2711-1CD10 SIRIUS S00 circuit breaker, 100 kA breaking capacity at 400 V AC. UL 489/CSA design. Sourced to order against RFQ. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2711-1CD10","Height":"144 mm","Upwards":"70 mm","Forwards":"0 mm","at 400 V":"gG 25 A","at 500 V":"gG 25 A","at 690 V":"gG 20 A","Backwards":"0 mm","Downwards":"70 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 2.5 A N-release 33 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"1 ... 10 mm², max. 2x 10 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"0.4 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"10 kA","Design Of The Product":"For system protection according to UL 489/CSA C22.2 No. 5","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"10 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"2.5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"2.5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","at AWG cables for main contacts":"2x (14 ... 10)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"1 ... 16 mm², max. 6 + 16 mm²","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2.5 ... 3 N·m","with high demand rate according to SN 31920":"50 %","shock resistance according to IEC 60068-2-27":"25 g / 11 ms (rectangular impulse and sine pulse)","Electrical Endurance (Operating Cycles) Typical":"100 000","at 480 AC Y/277 V according to UL 489 rated value":"65 kA","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/069e3a513974563a504666c247915d18.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=201422&mlfb=3RV2711-1CD10"},"ai":{"faq":[{"question":"Where can I buy 3RV2711-1CD10 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here."},{"question":"What is the breaking capacity of 3RV2711-1CD10 at 400 V?","answer":"100 kA at 400 V AC — that's the interrupting rating for a bolted fault on a 400 V bus."},{"question":"What compliance documentation does this breaker carry?","answer":"Designed for system protection per UL 489 and CSA C22.2 No. 5. The SIRIUS series typically ships with RoHS and REACH declarations; confirm with the order."},{"question":"Will 3RV2711-1CD10 drop into a panel specified for 3RV2311-1CC10?","answer":"Both are S00 frame breakers on 35 mm DIN rail with the same 45 mm width and M4 screw terminals, so the mechanical fit and wiring are identical. The difference is in the interrupting rating and trip curve — verify the 3RV2311-1CC10's specs against your fault current before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2711-1CD10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2711-1CD10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}