{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2711-1FD10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2711-1FD10","canonicalUrl":"https://aoctrl.com/siemens/3RV2711-1FD10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2711-1FD10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV2711-1FD10 circuit breaker, size S00, for system protection per UL 489/CSA C22.2 No.5, 100 kA interrupting at 400 V AC, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"The Siemens 3RV2711-1FD10 is a SIRIUS circuit breaker in frame size S00, designed specifically for system protection under UL 489 and CSA C22.2 No. 5. This means it's listed as a branch-circuit protective device for North American panels — not just a motor-protective breaker for IEC applications. The 100 kA interrupting rating at 400 V AC gives real SCCR headroom for high-fault installations; at 690 V AC it still clears 6 kA, so it handles mixed-voltage lineups without cascading upstream. ## Selectivity & coordination For a panel originally built around the 3RV2021-1FA15: the 3RV2711-1FD10 shares the S00 frame size and the same 45 mm width and 97 mm depth. The key difference is the UL 489 system-protection listing on this part versus the IEC motor-protective design of the 3RV2021-1FA15. If the existing panel requires a UL 489 listed branch-circuit device for compliance, the 3RV2711-1FD10 drops in without rewiring — same footprint, same terminal arrangement. For a pure IEC motor-starting application, the 3RV2021-1FA15 with its integrated overload function may be the better fit. ## Integration & wiring Terminal screws take a Pozidriv size 2 tip with a 5–6 mm shaft diameter. The M4 main-contact bolts are standard for S00 frame. Clearance: 70 mm upward, 70 mm downward, 30 mm to the side — no forward clearance needed.","metaTitle":"Siemens 3RV2711-1FD10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2711-1FD10 SIRIUS circuit breaker, size S00, rated 100 kA at 400 V AC. UL 489/CSA C22.2 No.5 system protection. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RV2711-1FD10","Height":"144 mm","Upwards":"70 mm","Forwards":"0 mm","at 400 V":"gG 32 A","at 500 V":"gG 32 A","at 690 V":"gG 25 A","Backwards":"0 mm","Downwards":"70 mm","At The Side":"30 mm","Rated Value":"20 ... 690 V","description":"Circuit breaker size S00 for system protection with approval circuit breaker UL 489, CSA C22.2 No.5-02 A-release 5 A N release 65 A screw terminal Standard switching capacity","During Storage":"-50 ... +80 °C","at AC-3 maximum":"15 1/h","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","at AC-3e maximum":"15 1/h","For Main Contacts":"M4","Mounting Position":"any","Solid Or Stranded":"1 ... 10 mm², max. 2x 10 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","at 230 V rated value":"1.1 kW","at 240 V rated value":"100 kA","at 400 V rated value":"100 kA","at 500 V rated value":"100 kA","at 690 V rated value":"4 kA","Design Of The Product":"For system protection according to UL 489/CSA C22.2 No. 5","Ground Fault Detection":"No","Phase Failure Detection":"No","For Main Current Circuit":"screw-type terminals","at AC at 240 V rated value":"100 kA","at AC at 400 V rated value":"100 kA","at AC at 500 V rated value":"100 kA","at AC at 690 V rated value":"6 kA","Design Of Screwdriver Shaft":"Diameter 5 to 6 mm","Size Of The Circuit-Breaker":"S00","Size Of The Screwdriver Tip":"Pozidriv size 2","at AC-3 rated value maximum":"690 V","Of The Main Contacts Typical":"100 000","at AC in hot operating state":"7.25 W","at AC-3 at 400 V rated value":"5 A","at AC-3e rated value maximum":"690 V","Of Auxiliary Contacts Typical":"100 000","Substance Prohibitance (Date)":"10/01/2009","at AC-3e at 400 V rated value":"5 A","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"5 A","at AWG cables for main contacts":"2x (14 ... 10)","Design Of The Short-Circuit Trip":"magnetic","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Display Version For Switching Status":"Handle","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2.4 W","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"1 ... 16 mm², max. 6 + 16 mm²","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","with low demand rate according to SN 31920":"50 FIT","For Main Contacts With Screw-Type Terminals":"2.5 ... 3 N·m","with high demand rate according to SN 31920":"50 %","shock resistance according to IEC 60068-2-27":"25 g / 11 ms (rectangular impulse and sine pulse)","Electrical Endurance (Operating Cycles) Typical":"100 000","at 480 AC Y/277 V according to UL 489 rated value":"65 kA","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"65 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$69.85","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a1208ea5ab97afd1613a9d68001ade83.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=157416&mlfb=3RV2711-1FD10"},"ai":{"faq":[{"question":"What is the interrupting rating of 3RV2711-1FD10 at 400 V?","answer":"100 kA at 400 V AC. At 690 V AC it clears 6 kA."},{"question":"Will 3RV2711-1FD10 replace 3RV2021-1FA15 in an existing panel?","answer":"Mechanically yes — same S00 frame, same 45 mm width, same DIN rail mount. Electrically the 3RV2711-1FD10 is a UL 489 system-protection breaker, not a motor-protective breaker with overload. Verify the circuit protection requirements before swapping."},{"question":"What compliance documentation does Siemens provide for 3RV2711-1FD10?","answer":"The part carries UL 489 and CSA C22.2 No. 5 listing. Standard Siemens documentation includes RoHS and REACH compliance declarations available through the product support portal."},{"question":"How do I get pricing and availability for 3RV2711-1FD10?","answer":"Submit an RFQ through this listing. The part is quoted to order with current pricing and availability confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2711-1FD10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2711-1FD10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}