{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2811-1GD10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2811-1GD10","canonicalUrl":"https://aoctrl.com/siemens/3RV2811-1GD10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2811-1GD10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, size S00, 3RV2811-1GD10, 100 kA breaking capacity at 400 V AC, for transformer protection per UL 489, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"## What the 100 kA rating means for the panel The Siemens 3RV2811-1GD10 is a SIRIUS circuit breaker sized S00, designed specifically for transformer protection per UL 489 and CSA C22.2 No.5. Any mounting position is permitted. Clearance requirements: 70 mm upward and downward, 30 mm to the side, zero forward or backward. Main circuit terminals accept 1 to 10 mm² solid or stranded, up to 2×10 mm²; screwdriver shaft diameter 5 to 6 mm, Pozidriv size 2 tip. ## Transformer-duty design Unlike a standard motor-protective circuit breaker, this unit is engineered for transformer inrush and overload characteristics per UL 489. The gG fuse coordination values at 400 V are 50 A, at 500 V 40 A, and at 690 V 35 A — these define the maximum backup fuse for the breaker's short-circuit rating. No ground-fault or phase-failure detection built in; external protection is needed for those functions.","metaTitle":"Siemens 3RV2811-1GD10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2811-1GD10 SIRIUS circuit breaker, size S00, 100 kA breaking capacity at 400 V AC. Designed for transformer protection per UL 489. Available to order — request quote for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"144 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.93","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8866307ccb4fb9b2d67b0c300553c91b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=364931&mlfb=3RV2811-1GD10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2811-1GD10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2811-1GD10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2811-1GD10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}