{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV2811-1HD10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV2811-1HD10","canonicalUrl":"https://aoctrl.com/siemens/3RV2811-1HD10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV2811-1HD10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, size S00, 3RV2811-1HD10, 100 kA breaking capacity at 400 V AC, screw and snap-on mounting on 35 mm DIN rail, for transformer protection per UL 489.","salesMarkdown":"The Siemens 3RV2811-1HD10 is a SIRIUS circuit breaker in frame size S00, designed specifically for transformer protection in accordance with UL 489 and CSA C22.2 No.5. The key spec that defines its real-world fit is the breaking capacity: 100 kA at 400 V AC (and at 240 V AC), 42 kA at 500 V AC, and 6 kA at 690 V AC. ## Transformer protection design and coordination This breaker is purpose-built for transformer protection, not general motor or feeder duty. The design per UL 489 means it handles the magnetizing inrush of a transformer without nuisance tripping, while still providing short-circuit and overload protection for the transformer and its secondary-side conductors. The rated operational voltage range is 20 to 690 V, covering most low-voltage transformer primaries. For selectivity and fuse coordination, the maximum permissible backup fuse ratings are specified per voltage: gG 50 A at 400 V, gG 40 A at 500 V, and gG 35 A at 690 V. This is critical for an engineer designing a coordinated protection scheme — the upstream fuse must not exceed these values to ensure the breaker clears a fault within its rated capacity. Dimensions are 97 mm deep, 45 mm wide, and 144 mm tall. Clearance requirements: 70 mm upwards and downwards, 30 mm to the side, and zero forwards or backwards — so it can be mounted flush against a back panel or enclosure wall. The main contact screw is M4, requiring a Pozidriv size 2 screwdriver tip with a shaft diameter of 5 to 6 mm. These are standard panel-building details — no special tooling needed.","metaTitle":"Siemens 3RV2811-1HD10 SIRIUS Circuit Breaker, 100 kA at 400","metaDescription":"Siemens 3RV2811-1HD10 SIRIUS circuit breaker, size S00, 100 kA breaking capacity at 400 V AC. Designed for transformer protection per UL 489. Screw/snap-on 35 mm DIN rail. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"97 mm","Width":"45 mm","Height":"144 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.93","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79e77125d84148ee5fc029fb2a78c140.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=229274&mlfb=3RV2811-1HD10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV2811-1HD10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV2811-1HD10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV2811-1HD10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}