{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV5011-0JA10-0FE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV5011-0JA10-0FE0","canonicalUrl":"https://aoctrl.com/siemens/3RV5011-0JA10-0FE0","factsUrl":"https://aoctrl.com/api/mcp/products/3RV5011-0JA10-0FE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV5011-0JA10-0FE0, motor protection circuit breaker, Size S00, Class 10, A-release 0.7-1A, N-release 13A, screw terminal, standard switching capacity.","salesMarkdown":"## Motor Protection Circuit Breaker, Size S00 It carries an A-release adjustable from 0.7 to 1 A for overload protection and a fixed N-release of 13 A for short-circuit protection, terminated via screw terminals with standard switching capacity. The 0.7-1 A A-release range sets the overload trip point for the motor full-load current — set it to match the motor nameplate FLA. Class 10 trip curve means it will trip within 10 seconds at 7.2× the set current, which is standard for standard induction motor starting (not for high-inertia loads that need Class 20 or 30). Size S00 fits the compact DIN-rail footprint common in control panels. ## Panel Integration Screw terminals accept 0.5-4 mm² conductors. The compact S00 frame leaves room for adjacent contactors and overload relays in the same row.","metaTitle":"Siemens 3RV5011-0JA10-0FE0 Motor Protection CB, 0.7-1A","metaDescription":"Siemens 3RV5011-0JA10-0FE0 motor protection circuit breaker, Size S00, Class 10, 0.7-1A. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621364&mlfb=3RV5011-0JA10-0FE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV5011-0JA10-0FE0/alternatives.json"},"ai":{"faq":[{"question":"What is the 3RV5011-0JA10-0FE0 used for?","answer":"It is a motor protection circuit breaker for protecting motors against overload and short-circuit. The adjustable A-release (0.7-1 A) sets the overload trip point; the fixed N-release (13 A) handles short-circuit faults. Class 10 trip characteristic suits standard induction motor starting."},{"question":"Where can I buy the 3RV5011-0JA10-0FE0?","answer":"We source this part to order against an RFQ. Submit a request for current pricing and availability — we confirm at quote time through our independent distribution network."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV5011-0JA10-0FE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV5011-0JA10-0FE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}