{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-0CA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-0CA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-0CA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0CA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6011-0CA10, size S00 motor protection circuit breaker, 3-pole, 0.25 A rated operational current, Class 10 trip, screw terminals, 45 mm width.","salesMarkdown":"## Panel integration — DIN footprint and clearances The 3RV6011-0CA10: Width 45 mm, depth 96 mm, height 97 mm. Any mounting position. Clearance: 50 mm upwards, 50 mm downwards, 30 mm at the side, 0 mm forwards and backwards. Panel-builder note: the 0 mm forward/backward clearance means it sits flush against the backplane or enclosure wall — no breathing gap needed for this frame size. Screw terminal torque: 0.8 to 1.2 N·m.","metaTitle":"Siemens 3RV6011-0CA10 SIRIUS Motor Protection CB, 0.25 A, Cl","metaDescription":"Siemens 3RV6011-0CA10 SIRIUS motor protection circuit breaker, 0.25 A rated current, Class 10 trip, size S00, 3-pole, screw terminals, 45 mm wide, active production, available to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"5 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.25 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"0.25 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.18 ... 0.25 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/972aba7207bae081a4d88bf90c9a2f4b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621638&mlfb=3RV6011-0CA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0CA10/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3RV6011-0CA10?","answer":"Rated operational current 0.25 A at AC-3 / 400 V, Trip Class 10, rated insulation voltage 690 V, operating frequency 50/60 Hz, surge voltage resistance 6 kV, power loss 5 W total typical."},{"question":"Will 3RV6011-0CA10 drop into a panel specified around 3RV1011-0GA10?","answer":"Both are size S00, 45 mm wide, 3-pole, screw terminals, same DIN rail footprint and clearance requirements. The 3RV6011-0CA10 is the standard-duty SIRIUS line; the 3RV1011-0GA10 is the high-performance variant with higher breaking capacity. Panel cutout and wiring are identical, but verify the available fault current at the panel — the 3RV1011 series carries a higher short-circuit breaking rating."},{"question":"Where can I buy 3RV6011-0CA10?","answer":"Sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-0CA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-0CA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}