{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-0HA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-0HA15","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-0HA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0HA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV6011-0HA15, 0.8 A, Class 10, 3-pole, size S00, screw terminals, 690 V, 50/60 Hz.","salesMarkdown":"It is a 3-pole device in the compact S00 frame size, rated for 690 V at AC-3 duty and 50/60 Hz. Power loss is 6 W typical. This is a current-production part (lifecycle stage: current). The 0.8 A rated current and Class 10 trip curve mean this breaker is sized for a small motor — fractional horsepower, say a 0.25 kW three-phase motor at 400 V. The 690 V AC-3 rating covers switching motor loads at line voltage up to that level. The S00 frame (45 mm wide, 96 mm deep, 97 mm high) fits the standard DIN-rail footprint; clearance requirements are 50 mm above and below, 30 mm to the sides, and zero forward/backward clearance needed. ## Integration — DIN rail and wiring Accepts 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²) solid or stranded wire on main contacts; AWG equivalents 2× (18 to 12) or 2× (20 to 16). Auxiliary contacts use screw terminals, 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²). Terminal torque for main contacts: 0.8 to 1.2 N·m. The transverse auxiliary switch design allows side-by-side ganging without extra spacing beyond the 30 mm side clearance.","metaTitle":"Siemens 3RV6011-0HA15 SIRIUS Motor Protection Breaker, 0.8 A","metaDescription":"Siemens 3RV6011-0HA15 SIRIUS motor protection circuit breaker, 0.8 A rated current, Class 10 trip, 690 V, 3-pole, size S00. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.8 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3 at 400 V rated value":"0.8 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"10 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.55 ... 0.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0fd42e7326c88606ad0e9efbe092fa25.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621649&mlfb=3RV6011-0HA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0HA15/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3RV6011-0HA15?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the closest functional second-source for 3RV6011-0HA15?","answer":"The closest functional peer is the 3RV6011-0CA10, which shares the same S00 frame, 3-pole design, screw terminals, and Class 10 trip. The key difference is the rated current — 3RV6011-0HA15 is 0.8 A, while 3RV6011-0CA10 is rated at a different current level. Verify the motor FLA before substituting."},{"question":"Will 3RV6011-0HA15 drop into a panel specified for 3RV6011-0CA10?","answer":"Yes — both are S00 frame size, same DIN-rail footprint, same screw-terminal layout, same 3-pole configuration. No rewiring or panel modification is needed for the physical fit. Only the current rating differs; confirm the 0.8 A setting matches the motor protection requirement."},{"question":"What compliance documentation does Siemens provide for 3RV6011-0HA15?","answer":"The part carries a substance prohibition date of 05/01/2012, indicating RoHS compliance. As a SIRIUS motor protection breaker, it is designed to meet IEC/EN 60947-4-1 and related standards. Specific UL, CSA, or REACH documentation should be confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-0HA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-0HA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}