{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-0JA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-0JA15","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-0JA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0JA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV6011-0JA15, 1 A rated operational current, Class 10 trip, 690 V AC-3, 50/60 Hz, size S00, screw-type terminals, for 35 mm DIN rail.","salesMarkdown":"## Motor protection circuit breaker, 1 A, Class 10 — panel fit and trip curve The magnetic short-circuit trip handles fault clearing independently of the thermal element. The S00 frame is compact: 45 mm wide, 97 mm tall, 96 mm deep. That 50 mm vertical gap is non-negotiable for arc-fault venting — don't crowd the enclosure top. Main and auxiliary/control circuits use screw-type terminals. Main contacts accept 2× (0.5 to 1.5 mm²) solid/stranded or 2× (0.75 to 2.5 mm²), or AWG 2× (18 to 12) and 2× (20 to 16). Auxiliary contacts accept 2× (0.5 to 1.5 mm²) or 2× (0.75 to 2.5 mm²), AWG 2× (20 to 16) and 2× (18 to 14). Torque for main contact screws: 0.8 to 1.2 N·m. Finely stranded wire requires ferrule processing.","metaTitle":"Siemens 3RV6011-0JA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-0JA15 SIRIUS motor protection circuit breaker, 1 A rated current, Class 10 trip, 690 V AC-3, 50/60 Hz, screw terminals, size S00. Active production. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3 at 400 V rated value":"1 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.7 ... 1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/09a243e7c79848e85558d384b8c10d8a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621651&mlfb=3RV6011-0JA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-0JA15/alternatives.json"},"ai":{"faq":[{"question":"What is the 3RV6011-0JA15 used for?","answer":"It is a motor protection circuit breaker for thermal-magnetic overload and short-circuit protection of motors up to 1 A, Class 10 trip, size S00, for 35 mm DIN rail mounting."},{"question":"What are the key ratings of the 3RV6011-0JA15?","answer":"Rated operational current 1 A, AC-3 rated voltage 690 V, operating frequency 50/60 Hz, trip class 10, power loss 6 W typical."},{"question":"Where can I buy the 3RV6011-0JA15?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-0JA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-0JA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}