{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1AA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1AA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1AA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1AA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV6011-1AA10, 3-pole, size S00, 1.6 A rated operational current, Class 10 trip, 690 V, screw terminals, 45 mm width.","salesMarkdown":"## Motor protection circuit breaker, 1.6 A, Class 10 — SIRIUS 3RV6011-1AA10 Its thermal overload release (Class 10) and magnetic short-circuit trip cover the two failure modes that kill a motor: sustained overload and a bolted fault. Rated for 690 V with a 6 kV surge voltage resistance, it handles standard 400 V line supplies with headroom for voltage swells. Depth of 96 mm and height of 97 mm mean it clears most 120 mm deep enclosures. Clearance requirements: 50 mm upwards and downwards, 30 mm at the sides; zero forwards or backwards — the breaker can sit flush against the back panel or door. Accepts 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm²; for AWG, 2x (18 to 12) or 2x (20 to 16). Finely stranded with ferrule: 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²). Tightening torque: 0.8 to 1.2 N·m. The 6 W total power loss is modest — no forced cooling needed in a standard enclosure, but group several of these in a sealed box and the heat adds up.","metaTitle":"Siemens 3RV6011-1AA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1AA10 SIRIUS motor protection circuit breaker, 1.6 A rated current, Class 10 trip, 690 V, 3-pole, size S00. Active production. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"1.6 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621654&mlfb=3RV6011-1AA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1AA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV6011-1AA10 and how do I get a price?","answer":"The 3RV6011-1AA10 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional alternative to 3RV6011-1AA10?","answer":"The closest functional peer is the 3RV6011-0CA10, which shares the same SIRIUS S00 frame size, 3-pole design, and Class 10 trip characteristic. The key difference is the rated current: the 3RV6011-1AA10 is set for 1.6 A, while the 3RV6011-0CA10 covers a different current range. They are not drop-in replacements — verify the motor FLA before substituting."},{"question":"Will 3RV6011-1AA10 fit in a panel designed for 3RV6011-0CA10?","answer":"Yes, the physical footprint is identical — both are size S00 with the same 45 mm width, 96 mm depth, and 97 mm height. The mounting method (snap-on 35 mm DIN rail) and clearance requirements are the same. No rewiring or panel modification is needed for the swap, provided the current rating matches the motor."},{"question":"What compliance documentation does Siemens provide for 3RV6011-1AA10?","answer":"The part is RoHS compliant with a substance prohibition date of 05/01/2012. It carries IEC/EN 60947 approvals for motor protection circuit breakers, with a 6 kV surge voltage resistance and 25 g / 11 ms shock resistance per IEC 60068-2-27. Standard Siemens documentation includes the declaration of conformity and CE marking."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1AA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1AA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}