{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1AA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1AA15","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1AA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1AA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6011-1AA15, motor protection circuit breaker, Size S00, 3-pole, 1.6 A rated operational current, Trip Class 10, screw terminals, 690 V, 50-60 Hz.","salesMarkdown":"The Siemens 3RV6011-1AA15 is a SIRIUS motor-protection circuit breaker in the S00 frame size, rated 1.6 A operational current at 690 V AC-3, 50-60 Hz. Trip Class 10 thermal overload release paired with a magnetic short-circuit trip — covers the two protection curves a motor branch needs: overload (thermal) and short-circuit (magnetic). The 1.6 A rating sets the full-load current it carries continuously; the magnetic trip clears faults fast enough to protect the downstream contactor and cable. Snap-on mounting onto 35 mm DIN rail per DIN EN 60715, screw-fastened as well. 45 mm wide, 97 mm tall, 96 mm deep — fits a standard S00 footprint. Mounting position any, so vertical or horizontal panel layouts work. Clearance: 50 mm above and below, 30 mm at the sides, zero forward or backward — lets you pack rows tight if the heat rise stays within the -20 to +60 °C operating range. Accepts 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded, AWG 18–12 for main contacts. Torque 0.8–1.2 N·m. Typical power loss 6 W total — negligible in a ventilated enclosure but factor into a sealed panel's thermal budget.","metaTitle":"Siemens 3RV6011-1AA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1AA15 SIRIUS motor protection circuit breaker, 1.6 A rated current, Trip Class 10, 690 V, 3-pole, screw terminals, DIN rail mount. Active lifecycle. Available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","for AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3 at 400 V rated value":"1.6 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"21 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/68c22c5e4b36ea109dbe8436a4e171a9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621255&mlfb=3RV6011-1AA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1AA15/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RV6011-1AA15?","answer":"The 3RV6011-0CA10 is a close functional peer in the same S00 frame and Class 10, but verify the rated current — the 3RV6011-1AA15 is set at 1.6 A, while the 0CA10 covers a different current range. Both share the same DIN rail footprint, screw terminals, and thermal-magnetic release design, so a panel laid out for one can accept the other without rewiring, provided the current setting matches the motor FLA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1AA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1AA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}