{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1CA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1CA15","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1CA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1CA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV6011-1CA15, 2.5 A rated operational current, Class 10 trip, 690 V AC-3, 3-pole, screw terminals, frame size S00.","salesMarkdown":"The 45 mm width and 96 mm depth fit standard S00 panel layouts. Screw-type terminals on both main and auxiliary circuits accept 2x (0.5 to 1.5 mm²) solid or stranded, or 2x (0.75 to 2.5 mm²). AWG equivalents: 2x (18 to 12) for main contacts, 2x (20 to 16) for auxiliary. Torque to 0.8 to 1.2 N·m. ## Rating context and so-what Rated 2.5 A at AC-3 for switching motor loads — that is the current the breaker will carry continuously and trip on overload, not the short-circuit rating. Maximum switching frequency at AC-3 is 15 operations per hour. Thermal overload release protects against sustained overcurrent; magnetic short-circuit trip handles fault clearing. Surge voltage resistance rated at 6 kV, shock tested to 25 g / 11 ms per IEC 60068-2-27. Ambient operating range -20 to +60 °C, storage -50 to +80 °C, with 10 to 95 % relative humidity.","metaTitle":"Siemens 3RV6011-1CA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1CA15 SIRIUS motor protection circuit breaker, 2.5 A rated current, Class 10 thermal-magnetic trip, 690 V AC-3, screw terminals, DIN rail mount. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3 at 400 V rated value":"2.5 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.8 ... 2.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b1fd4a7533c4693ba9cfcc45254a605f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621259&mlfb=3RV6011-1CA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1CA15/alternatives.json"},"ai":{"faq":[{"question":"What is 3RV6011-1CA15's depth and width?","answer":"Depth is 96 mm, width is 45 mm, height is 97 mm. These dimensions match the S00 frame size."},{"question":"Will 3RV6011-1CA15 drop into a panel specified around 3RV6011-0CA10?","answer":"Both are S00 frame size motor protection breakers with the same mounting footprint (snap-on 35 mm DIN rail) and terminal layout. The 3RV6011-1CA15 should physically fit without rewiring, but verify the current rating difference — the -1CA15 is 2.5 A, while the -0CA10 is a different rating. Check your BOM for the correct trip current."},{"question":"How do I get current pricing and availability for 3RV6011-1CA15?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution channels."},{"question":"What compliance documentation does this part carry?","answer":"RoHS compliance is indicated by the substance prohibition date of 05/01/2012. The part is designed to IEC standards for motor protection circuit breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1CA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1CA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}