{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, motor protection circuit breaker, 3RV6011-1JA10, 10 A rated operational current, CLASS 10 trip, 690 V AC-3, 45 mm wide, screw and snap-on 35 mm DIN rail mounting.","salesMarkdown":"Its thermal overload release (CLASS 10) and magnetic short-circuit trip work together to clear faults before the motor insulation or upstream contactor takes damage. The 10 A rated operational current at AC-3, 400 V means it directly protects a motor drawing up to that full-load current in a standard 400 V line. The 45 mm width (three 15 mm modules) fits a standard distribution board or motor control centre slot. Screw-type terminals on top and bottom accept 2x (0.75 to 2.5 mm²) solid/stranded or 2x 4 mm², torque to 0.8–1.2 N·m. Operates from -20 to +60 °C, stores from -50 to +80 °C, and handles 10–95 % relative humidity. Shock rated at 25 g / 11 ms per IEC 60068-2-27, surge voltage resistance at 6 kV. The 50/60 Hz AC-3 rating at 690 V maximum covers most global industrial supplies. Power loss totals 7 W typical — negligible for panel thermal budgeting.","metaTitle":"Siemens 3RV6011-1JA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1JA10 SIRIUS motor protection circuit breaker, 10 A rated operational current, CLASS 10 trip, 690 V AC-3, 45 mm wide, screw and snap-on DIN rail mount. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"130 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$194.13","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/96bde2f7ad9eb59e188a5e9d78b1b58d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621270&mlfb=3RV6011-1JA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1JA10/alternatives.json"},"ai":{"faq":[{"question":"Is 3RV6011-1JA10 available via RFQ confirmation and what is the lead time for an order?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is 3RV6011-1JA10's listed depth (96 mm) on this component line?","answer":"The depth is 96 mm."},{"question":"What is 3RV6011-1JA10's listed width (45 mm) on this component line?","answer":"The width is 45 mm."},{"question":"What compliance documentation does this brand provide for 3RV6011-1JA10 (RoHS, REACH, UL, IEC)?","answer":"The part carries a substance prohibitance date of 05/01/2012, indicating RoHS compliance. It is designed for motor protection per IEC standards, with shock resistance tested to IEC 60068-2-27 and surge voltage resistance rated at 6 kV."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}