{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1JA15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1JA15","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1JA15","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1JA15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6011-1JA15, motor protection circuit breaker, size S00, 10 A rated operational current, Class 10 trip, 690 V, screw terminals, for 35 mm DIN rail.","salesMarkdown":"It combines a thermal overload release (Class 10) and a magnetic short-circuit release in one 3-pole device, sized for a 10 A rated operational current at 690 V AC-3. The 7 W typical power loss stays manageable inside a crowded panel. The magnetic trip handles instantaneous short-circuit clearing without waiting for the thermal element. ## Where it fits — panel and mounting The S00 footprint — 45 mm wide, 96 mm deep, 97 mm tall — fits standard 45 mm-wide DIN slots; clearance requirements are 50 mm upward and downward, 30 mm to the side, and zero forward/backward. That tight clearance profile makes it practical for dense terminal-block layouts. Screw-type terminals on both main and auxiliary circuits accept 2x (0.5…1.5 mm²) solid/stranded or 2x (0.75…2.5 mm²) — AWG equivalents 18–12 for mains, 20–16 for auxiliary. Terminal torque range is 0.8…1.2 N·m. Rated for -20…+60 °C operating ambient, 10…95 % relative humidity, and -50…+80 °C storage/transport. Shock resistance per IEC 60068-2-27 is 25 g / 11 ms — suitable for installation on machinery subject to moderate shock.","metaTitle":"Siemens 3RV6011-1JA15 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1JA15 SIRIUS motor protection circuit breaker, 10 A rated current, Class 10 trip, 690 V, size S00, DIN rail mount. Current lifecycle stage. Sourced to order; quote","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Auxiliary Switch":"transverse","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","For Auxiliary And Control Circuit":"screw-type terminals","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","For Auxiliary Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"130 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","breaking capacity maximum short-circuit current (Icu) at AC at 400 V rated value":"100 kA","breaking capacity operating short-circuit current (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b882bf8a0c8373850250c488aee272de.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621271&mlfb=3RV6011-1JA15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1JA15/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV6011-1JA15?","answer":"The 3RV6011-0CA10 is a sibling in the same S00 frame and Class 10 family, but it carries a lower current rating. Verify the load current before substituting — the 3RV6011-1JA15 is set for 10 A operational current, while the -0CA10 is a different amp setting. They share the same DIN footprint and terminal layout, so a swap is mechanically possible if the rating matches your motor FLA."},{"question":"What are the key dimensions of 3RV6011-1JA15?","answer":"Width is 45 mm, depth 96 mm, height 97 mm. Clearances: 50 mm above and below, 30 mm to the side, zero forward or backward. Mounts on 35 mm DIN rail."},{"question":"Where can I buy 3RV6011-1JA15 and how is it quoted?","answer":"It is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — volume quotes are handled on request."},{"question":"What compliance documentation does 3RV6011-1JA15 carry?","answer":"RoHS compliant as of May 1, 2012. Rated for 50/60 Hz networks, 690 V insulation voltage, 6 kV surge resistance. Operating range -20…+60 °C, storage -50…+80 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1JA15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1JA15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}