{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-1KA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-1KA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-1KA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1KA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS motor protection circuit breaker, 3RV6011-1KA10, size S00, 12.5 A rated operational current, Class 10 trip, thermal-magnetic overload and short-circuit release, 690 V, 50/60 Hz, screw-type terminals, snap-on 35 mm DIN rail.","salesMarkdown":"The Siemens SIRIUS 3RV6011-1KA10 is a motor protection circuit breaker in the compact S00 frame size, rated 12.5 A operational current at AC-3 duty (400 V). Thermal overload release handles sustained overcurrent; magnetic short-circuit trip clears faults instantly. Screw-type terminals accept 2x (0.75 to 2.5 mm²) solid/stranded or 2x 4 mm²; torque to 0.8–1.2 N·m. Rated for 50/60 Hz, 690 V max (AC-3). Power loss 7 W typical. Surge voltage resistance 6 kV. Shock rated 25 g / 11 ms per IEC 60068-2-27. Operating temperature -20 to +60 °C. Installation altitude up to 2000 m. Relative humidity 10–95 %. RoHS compliance date 05/01/2012.","metaTitle":"Siemens 3RV6011-1KA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-1KA10 SIRIUS motor protection circuit breaker, 12.5 A rated current, Class 10 trip, thermal-magnetic, 690 V, 50/60 Hz, screw terminals, size S00. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"12.5 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"12.5 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"163 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"9 ... 12.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d799bdb06d766a328b7097eed47cc0f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621272&mlfb=3RV6011-1KA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-1KA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV6011-1KA10 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figure is published here."},{"question":"What is the closest functional alternative to 3RV6011-1KA10?","answer":"The 3RV6011-0CA10 is a lower-current sibling in the same S00 frame and Class 10 trip family. The 1KA10 carries a 12.5 A rating versus the 0CA10's lower amp setting — verify your motor FLA before substituting. Both share the same DIN footprint, terminal style, and thermal-magnetic design."},{"question":"What compliance documentation does Siemens provide for 3RV6011-1KA10?","answer":"RoHS compliance is documented with a substance prohibition date of 05/01/2012. The part is designed to meet applicable IEC and UL standards for motor protection circuit breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-1KA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-1KA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}