{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6011-4AA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6011-4AA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6011-4AA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6011-4AA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6011-4AA10, Size S00 motor protection circuit breaker, 3-pole, 16 A rated operational current, Class 10 trip, screw terminals, 45 mm width, 96 mm depth.","salesMarkdown":"The Siemens 3RV6011-4AA10 is a SIRIUS Size S00 motor protection circuit breaker, 3-pole, rated 16 A operational current with a thermal-magnetic trip — thermal overload release for Class 10 protection, magnetic short-circuit release for fault clearing. It's the dedicated overcurrent and short-circuit protector for a 3-phase motor branch circuit, sized for the S00 frame's compact DIN-rail footprint. Rated insulation voltage 690 V, AC-3 switching at 400 V carries the full 16 A — that's the motor-rated current for a standard 3-phase induction motor up to roughly 7.5 kW at 400 V. 45 mm wide, 97 mm tall, 96 mm deep — snaps onto 35 mm DIN rail per DIN EN 60715, or screws direct to a backplate. Screw-type terminals on top and bottom accept 2×(0.75–2.5 mm²) solid/stranded or 2×4 mm² solid; AWG 2×(18–12) solid, 2×(20–16) stranded. Torque to 0.8–1.2 N·m. The S00 frame keeps the wiring gutters clear — no need to oversize the enclosure for this breaker. RoHS compliant with substance prohibition date 05/01/2012. The SIRIUS series carries IEC/EN 60947-2 and 60947-4-1 certifications for motor protection and circuit-breaking duty. Shock resistance 25 g / 11 ms per IEC 60068-2-27; operating temperature -20 to +60 °C, storage -50 to +80 °C. Relative humidity 10–95 % during operation.","metaTitle":"Siemens 3RV6011-4AA10 SIRIUS Motor Protection Circuit Breake","metaDescription":"Siemens 3RV6011-4AA10 SIRIUS motor protection circuit breaker, 16 A rated current, Class 10 trip, 3-pole, Size S00, 45 mm wide, screw terminals. Active production, sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for motor protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"16 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"16 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"55 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"30 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621274&mlfb=3RV6011-4AA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6011-4AA10/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV6011-4AA10 drop into a panel specified around 3RV6011-0CA10 without rewiring?","answer":"Both are Size S00, 3-pole, same 45 mm width and DIN-rail mounting. The 3RV6011-4AA10 is rated 16 A; the 3RV6011-0CA10 is a lower-current variant. If the existing panel wiring and upstream protection are sized for 16 A, the swap is a direct mechanical fit — same footprint, same terminal layout."},{"question":"What is 3RV6011-4AA10's width and depth for panel layout?","answer":"Width 45 mm, depth 96 mm, height 97 mm. Clearance: 50 mm above and below, 30 mm at sides, zero forward or backward. Snaps onto 35 mm DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6011-4AA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6011-4AA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}