{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6311-0FC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6311-0FC10","canonicalUrl":"https://aoctrl.com/siemens/3RV6311-0FC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6311-0FC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker for starter combinations, 3RV6311-0FC10, S00 frame, 3-pole, 0.5 A rated operational current at AC-3/400 V, screw-type terminals, 35 mm DIN rail snap-on mounting.","salesMarkdown":"Instantaneous short-circuit trip responds at 6.5 A. Insulation voltage is 690 V at pollution degree 3; surge voltage withstand is 6 kV. The S00 frame size gives a footprint of 45 mm wide, 97 mm tall, and 96 mm deep. That 96 mm depth means it sits flush with the backplane on a standard 100 mm-deep enclosure; if you are retrofitting into an existing panel that was laid out for the physically identical S00 frame (like the 3RV6011 series), the footprint and rail clip are the same — no rewiring of the bus bars needed provided the terminal arrangement is top-and-bottom as listed.","metaTitle":"Siemens 3RV6311-0FC10 SIRIUS Circuit Breaker, 0.5 A, S00 Fra","metaDescription":"Siemens 3RV6311-0FC10 SIRIUS circuit breaker for starter combinations. Rated 0.5 A at AC-3/400 V, 690 V insulation, S00 frame. Screw and snap-on 35 mm DIN rail. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for starter combinations","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"5 W","Substance Prohibitance (Date)":"05/01/2012","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.5 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"0.5 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"6.5 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","breaking capacity maximum short-circuit current (Icu) at AC at 400 V rated value":"100 kA","breaking capacity operating short-circuit current (Ics) at AC at 400 V rated value":"100 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d9d78ddb283304246f74aa00b73e7f8e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621297&mlfb=3RV6311-0FC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6311-0FC10/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV6311-0FC10 drop into a panel designed for 3RV6011-0CA10?","answer":"Yes, provided the panel uses a 35 mm DIN rail per DIN EN 60715. Both parts share the S00 frame footprint and the same screw-and-snap-on mounting method. The terminal arrangement is top and bottom, so the bus-bar layout should be identical."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6311-0FC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6311-0FC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}