{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6311-1CC10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6311-1CC10","canonicalUrl":"https://aoctrl.com/siemens/3RV6311-1CC10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6311-1CC10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, circuit breaker for starter combinations, 3RV6311-1CC10, size S00, 2.5 A rated operational current, 690 V AC-3, screw-type terminals, snap-on 35 mm DIN rail.","salesMarkdown":"Rated 2.5 A operational current at AC-3 (690 V max), it handles motor switching duty up to that current, with a magnetic short-circuit trip set at 33 A instantaneous. That trip point is the key selectivity number: below 33 A, overloads ride through; above it, the breaker clears before downstream components take damage. Size S00 frame — 45 mm wide, 97 mm tall, 96 mm deep — so it occupies a standard single-module width on the rail. That 96 mm depth is the dimension to check against enclosure depth when the breaker sits behind a door or inside a shallow cabinet.","metaTitle":"Siemens 3RV6311-1CC10 SIRIUS Circuit Breaker, 2.5 A, 690 V","metaDescription":"Siemens SIRIUS 3RV6311-1CC10 circuit breaker for starter combinations, 2.5 A rated at 690 V AC-3. Screw terminals, size S00, snap-on DIN rail. Active production. Sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for starter combinations","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"2.5 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"2.5 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621304&mlfb=3RV6311-1CC10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6311-1CC10/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RV6311-1CC10?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is actively produced and sourced through independent distribution."},{"question":"Will 3RV6311-1CC10 drop into a panel that was specified around 3RV6011-0CA10 without rewiring?","answer":"Both are size S00 frame breakers with the same 45 mm width and screw-type terminals, so the mechanical fit and wiring footprint are identical. The difference is electrical: 3RV6311-1CC10 is rated 2.5 A with a 33 A magnetic trip, while the 3RV6011-0CA10 carries a different current rating and trip setting — verify the load's full-load amps and short-circuit requirements before swapping."},{"question":"What compliance documentation does this brand provide for 3RV6311-1CC10?","answer":"The part has a substance prohibition date of 05/01/2012, indicating RoHS compliance from that date. Expect RoHS and REACH declarations with the shipment; UL and IEC certifications are standard for the SIRIUS series but are not individually listed in this record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6311-1CC10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6311-1CC10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}