{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-0AA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-0AA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-0AA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-0AA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV6411-0AA10, for transformer protection, 0.16 A rated current, Class 10 trip, 690 V, 3-pole, S00 frame, screw terminals.","salesMarkdown":"That 96 mm depth is the body only; factor in wiring space for the screw-type terminals (top and bottom entry, 2x 0.75–2.5 mm² solid/stranded or 2x 4 mm²). ## Ratings and Application Context The 0.16 A rating at AC-3 (400 V) is the motor-switching current — for transformer primary protection, the thermal Class 10 curve matches the inrush characteristic of small control transformers. Rated operational voltage is 690 V, surge voltage resistance 6 kV. Operating frequency 50/60 Hz, maximum switching rate 15 operations per hour at AC-3. Shock resistance 25g / 11 ms per IEC 60068-2-27. Installation altitude up to 2000 m. Lifecycle stage is current — no phase-out or last-time-buy announced. The part carries a RoHS compliance date of 05/01/2012, confirming exemption-free substance compliance from that date.","metaTitle":"Siemens 3RV6411-0AA10 SIRIUS Circuit Breaker, 0.16 A, Class","metaDescription":"Siemens SIRIUS 3RV6411-0AA10 circuit breaker for transformer protection. 0.16 A rated current, Class 10 trip, 690 V, 3-pole, S00 frame. Active production. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"5 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.16 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"0.16 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"3.3 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.11 ... 0.16 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/da40da4d869b822e0d3eb97fb3b3aeed.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621321&mlfb=3RV6411-0AA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-0AA10/alternatives.json"},"ai":{"faq":[{"question":"Will 3RV6411-0AA10 drop into a panel that was specified around 3RV6011-0CA10 without rewiring?","answer":"Both parts share the S00 frame size and the same DIN-rail mounting pattern, so the mechanical footprint is identical. Terminal positions and wiring capacity should be verified against the original panel layout, but the physical swap is straightforward."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-0AA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-0AA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}