{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-0GA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-0GA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-0GA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-0GA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV6411-0GA10, for transformer protection, 0.63 A, Class 10, 3-pole, Size S00, screw-type terminals, snap-on DIN rail mounting.","salesMarkdown":"Three poles, Size S00 frame, screw-type terminals top and bottom. The S00 frame takes 45 mm width and 96 mm depth — fits standard 45 mm module spacing in a panel. Mounting position any orientation; clearance needs 50 mm above and below, 30 mm to the side for heat dissipation. Ambient during operation -20 to +60 °C, so it's fine inside a closed panel with other heat sources. Rated operational voltage 690 V, surge voltage resistance 6 kV. Thermal overload release paired with magnetic short-circuit trip. Power loss 5 W typical at rated current.","metaTitle":"Siemens 3RV6411-0GA10 SIRIUS Circuit Breaker, 0.63 A, Class","metaDescription":"Siemens 3RV6411-0GA10 SIRIUS circuit breaker for transformer protection, 0.63 A rated, Class 10 trip, 690 V, 3-pole, Size S00. Current lifecycle stage. Sourced to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"5 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"0.63 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"0.63 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"13 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","breaking capacity maximum short-circuit current (Icu) at AC at 400 V rated value":"100 kA","breaking capacity operating short-circuit current (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e049da97566ff1c8d4e839a08e1a3837.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621327&mlfb=3RV6411-0GA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-0GA10/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RV6411-0GA10?","answer":"The 3RV6011-0CA10 is the motor-protection variant in the same S00 frame — same footprint, same DIN rail mount, but its overload curve and magnetic trip are calibrated for motor starting, not transformer inrush. For transformer duty, stick with the 3RV6411-0GA10."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-0GA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-0GA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}