{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-1AA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-1AA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-1AA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1AA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker for transformer protection, 3RV6411-1AA10, 1.6 A rated operational current, Class 10, 690 V, 50/60 Hz, size S00, screw-type terminals, 45 mm width.","salesMarkdown":"## Part identification and function It combines a thermal overload release (Class 10) with a magnetic short-circuit trip in a three-pole package, rated at 1.6 A operational current at 400 V AC-3 duty and 690 V maximum. The 50/60 Hz operating frequency matches standard mains supplies for transformer primary-side protection in control panels. Dimensions: 45 mm wide, 97 mm high, 96 mm deep. Clearance requirements: 50 mm upward, 50 mm downward, 30 mm to the side; zero forward or backward clearance needed. Any mounting position allowed. Screw-type terminals for the main circuit accept 2x (0.75–2.5 mm²) solid/stranded or 2x 4 mm², with torque range 0.8–1.2 N·m. The active lifecycle means no last-time-buy constraints apply.","metaTitle":"Siemens 3RV6411-1AA10 SIRIUS Circuit Breaker, 1.6 A, Class 1","metaDescription":"Siemens 3RV6411-1AA10 SIRIUS circuit breaker for transformer protection, 1.6 A rated, Class 10 trip, 690 V, 50/60 Hz. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"1.6 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"1.6 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"33 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"1.1 ... 1.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e149eda90899039453bb938ab542889.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621331&mlfb=3RV6411-1AA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1AA10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RV6411-1AA10 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3RV6411-1AA10 drop into a panel that was specified around 3RV6011-0CA10 without rewiring?","answer":"Both are size S00 SIRIUS breakers with the same 45 mm width and DIN-rail mounting, so panel cutout and rail position are identical. However, verify the terminal arrangement — the 3RV6411-1AA10 uses screw-type terminals for the main circuit; the 3RV6011-0CA10 may differ in terminal style or auxiliary contact configuration. No rewiring of the main power circuit should be needed, but auxiliary wiring should be checked against the specific terminal layout."},{"question":"What compliance documentation does this brand provide for 3RV6411-1AA10?","answer":"The part is RoHS compliant with a substance prohibitance date of May 1, 2012. It carries a 6 kV rated surge voltage resistance and is designed to IEC standards including IEC 60068-2-27 for shock resistance. Standard Siemens SIRIUS documentation includes the datasheet, operating instructions, and CE declaration of conformity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-1AA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-1AA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}