{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-1GA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-1GA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-1GA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1GA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker, 3RV6411-1GA10, for transformer protection, 3-pole, size S00, rated current 6.3 A, Trip Class 10, 690 V, screw terminals, DIN rail mount.","salesMarkdown":"## Transformer-protection circuit breaker, 6.3 A, Class 10 The magnetic short-circuit trip handles fault clearing, and the breaker is rated for 690 V AC at AC-3 duty. Any mounting position is allowed. Clearance: 50 mm upwards and downwards, 30 mm at the side, zero forwards or backwards. Panel builders can plan for the 45 mm width and 96 mm depth footprint. Rated operational current of 6.3 A at AC-3 (400 V) means this breaker is sized for the inrush and running current of a transformer up to that load. The 690 V rated value covers most 400/480 V systems with headroom. Relative humidity 10 to 95 %. Installation altitude up to 2000 m. Shock resistance 25 g / 11 ms per IEC 60068-2-27. RoHS compliance date 05/01/2012 (substance prohibitance).","metaTitle":"Siemens 3RV6411-1GA10 SIRIUS Circuit Breaker, 6.3 A, Class 1","metaDescription":"Siemens 3RV6411-1GA10 SIRIUS circuit breaker for transformer protection, 6.3 A rated current, Class 10, 690 V, 3-pole, screw terminals, DIN rail mount. Active production, sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"6 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"6.3 A","Design Of The Short-Circuit Trip":"magnetic","for AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"6.3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"130 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"4.5 ... 6.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7c1df6c9ba8854bc2f6d1d36d5cd5815.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621337&mlfb=3RV6411-1GA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1GA10/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RV6411-1GA10?","answer":"The 3RV6011-0CA10 is a peer in the same SIRIUS family but has different ratings; verify fit against your BOM line before substituting."},{"question":"What are the key ratings of 3RV6411-1GA10?","answer":"Rated operational current 6.3 A at AC-3 (400 V), Trip Class 10, rated voltage 690 V, 3-pole, size S00."},{"question":"Where can I buy 3RV6411-1GA10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-1GA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-1GA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}