{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-1HA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-1HA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-1HA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1HA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS circuit breaker for transformer protection, 3RV6411-1HA10, 8 A rated current, Class 10 trip, 690 V, 3-pole, Size S00, screw terminals, DIN rail mount.","salesMarkdown":"Rated for 690 V at AC-3 and 50/60 Hz, it's a 3-pole unit in the compact Size S00 frame (45 mm wide, 97 mm high, 96 mm deep) that screws or snaps onto 35 mm DIN rail per DIN EN 60715. Power loss is 7 W total typical. Screw-type terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm², with a tightening torque of 0.8 to 1.2 N·m. ## Panel Integration At 45 mm wide, three units fit in a 140 mm DIN section, leaving room for a 4-pole contactor alongside. Screw terminals top and bottom keep the wiring plane clean for panel builders. The Size S00 frame means it shares the same footprint as the SIRIUS 3RV2 contactor range for a coordinated motor starter assembly. Rated surge voltage resistance is 6 kV, and shock resistance per IEC 60068-2-27 is 25 g for 11 ms. Installation altitude is maximum 2,000 m above sea level.","metaTitle":"Siemens 3RV6411-1HA10 SIRIUS Circuit Breaker, 8 A, Class 10,","metaDescription":"Siemens 3RV6411-1HA10 SIRIUS circuit breaker for transformer protection. 8 A rated current, Class 10 trip, 690 V, DIN rail mount. Current lifecycle. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"8 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"8 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"163 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"5.5 ... 8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d83dc31c9da580d71c7dd5399ba6b567.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621338&mlfb=3RV6411-1HA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1HA10/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RV6411-1HA10?","answer":"The depth is 96 mm, with a width of 45 mm and height of 97 mm."},{"question":"What compliance documentation does this part carry?","answer":"RoHS compliance is documented with a substance prohibitance date of May 1, 2012. The part is designed to IEC standards for shock (IEC 60068-2-27) and surge voltage (6 kV)."},{"question":"Where can I buy 3RV6411-1HA10 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-1HA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-1HA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}