{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-1JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-1JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-1JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6411-1JA10 circuit breaker, size S00, for transformer protection, 10 A rated operational current, 690 V, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker, SIRIUS 3RV6411-1JA10 Its Trip Class 10 thermal overload release and magnetic short-circuit trip are sized for the inrush characteristics of control transformers and similar inductive loads — the thermal curve matches the heating time constant of a transformer winding, so nuisance tripping on magnetizing inrush is minimized. Rated operational frequency is 50 to 60 Hz, and total power loss is 7 W — a figure to include in enclosure thermal calculations when the breaker is grouped with other SIRIUS components. ## Integration and mounting details Size S00 frame (96 mm depth, 45 mm width, 97 mm height) with screw-type terminals on top and bottom for the main current circuit. Terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm² solid; AWG equivalents are 2x (18 to 12) and 2x (20 to 16). Tightening torque for main contacts is 0.8 to 1.2 N·m. Clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the side; zero clearance forwards or backwards — useful for panel layout when grouping multiple breakers. Relative humidity during operation spans 10 to 95 %. Shock resistance rated at 25 g / 11 ms per IEC 60068-2-27, and surge voltage resistance at 6 kV. Maximum installation altitude is 2 000 m above sea level. Substance prohibitance (RoHS) compliance date is 05/01/2012, indicating the part meets EU RoHS requirements from that date forward.","metaTitle":"Siemens 3RV6411-1JA10 SIRIUS Circuit Breaker, 10 A, Class 10","metaDescription":"Siemens 3RV6411-1JA10 SIRIUS circuit breaker for transformer protection. 10 A rated current, 690 V, Trip Class 10, size S00. Screw and snap-on DIN rail mount. Active lifecycle, ava","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Upwards":"50 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"50 mm","Trip Class":"CLASS 10","At The Side":"30 mm","Rated Value":"690 V","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715","Mounting Position":"any","Solid Or Stranded":"2x (0,75 ... 2,5 mm²), 2x 4 mm²","Product Brand Name":"SIRIUS","Product Designation":"Circuit breaker","Design Of The Product":"for transformer protection","For Main Current Circuit":"screw-type terminals","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","power loss [W] total typical":"7 W","Substance Prohibitance (Date)":"05/01/2012","Design Of The Overload Release":"thermal","Operating Frequency Rated Value":"50 ... 60 Hz","Operational Current Rated Value":"10 A","at AWG cables for main contacts":"2x (18 to 12), 2x (20 to 16)","Design Of The Short-Circuit Trip":"magnetic","Relative Humidity During Operation":"10 ... 95 %","operating frequency at AC-3 maximum":"15 1/h","Surge Voltage Resistance Rated Value":"6 kV","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","For Main Contacts With Screw-Type Terminals":"0.8 ... 1.2 N·m","shock resistance according to IEC 60068-2-27":"25g / 11 ms","operational current at AC-3 at 400 V rated value":"10 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Arrangement Of Electrical Connectors For Main Current Circuit":"Top and bottom","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"208 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","maximum short-circuit current breaking capacity (Icu) at AC at 400 V rated value":"100 kA","operating short-circuit current breaking capacity (Ics) at AC at 400 V rated value":"100 kA","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"7 ... 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ed06380cd812569680d54f28d29c562.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621339&mlfb=3RV6411-1JA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1JA10/alternatives.json"},"ai":{"faq":[{"question":"What is the 3RV6411-1JA10 used for?","answer":"It is a circuit breaker designed for transformer protection, with a thermal overload release (Trip Class 10) and magnetic short-circuit trip, rated at 10 A and 690 V."},{"question":"What are the key dimensions of 3RV6411-1JA10?","answer":"Depth is 96 mm, width is 45 mm, and height is 97 mm. Clearance needed: 50 mm upwards, 50 mm downwards, and 30 mm at the side."},{"question":"Does 3RV6411-1JA10 comply with RoHS?","answer":"Yes, the substance prohibitance compliance date is 05/01/2012, confirming EU RoHS compliance from that date."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-1JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-1JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}