{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RV6411-1JA10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RV6411-1JA10","canonicalUrl":"https://aoctrl.com/siemens/3RV6411-1JA10","factsUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1JA10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RV6411-1JA10 circuit breaker, size S00, for transformer protection, 10 A rated operational current, 690 V, Trip Class 10, screw and snap-on mounting onto 35 mm DIN rail.","salesMarkdown":"## Transformer-protection circuit breaker, SIRIUS 3RV6411-1JA10 Its Trip Class 10 thermal overload release and magnetic short-circuit trip are sized for the inrush characteristics of control transformers and similar inductive loads — the thermal curve matches the heating time constant of a transformer winding, so nuisance tripping on magnetizing inrush is minimized. Rated operational frequency is 50 to 60 Hz, and total power loss is 7 W — a figure to include in enclosure thermal calculations when the breaker is grouped with other SIRIUS components. ## Integration and mounting details Size S00 frame (96 mm depth, 45 mm width, 97 mm height) with screw-type terminals on top and bottom for the main current circuit. Terminals accept 2x (0.75 to 2.5 mm²) solid or stranded, or 2x 4 mm² solid; AWG equivalents are 2x (18 to 12) and 2x (20 to 16). Tightening torque for main contacts is 0.8 to 1.2 N·m. Clearance requirements: 50 mm upwards, 50 mm downwards, 30 mm at the side; zero clearance forwards or backwards — useful for panel layout when grouping multiple breakers. Relative humidity during operation spans 10 to 95 %. Shock resistance rated at 25 g / 11 ms per IEC 60068-2-27, and surge voltage resistance at 6 kV. Maximum installation altitude is 2 000 m above sea level. Substance prohibitance (RoHS) compliance date is 05/01/2012, indicating the part meets EU RoHS requirements from that date forward.","metaTitle":"Siemens 3RV6411-1JA10 SIRIUS Circuit Breaker, 10 A, Class 10","metaDescription":"Siemens 3RV6411-1JA10 SIRIUS circuit breaker for transformer protection. 10 A rated current, 690 V, Trip Class 10, size S00. Screw and snap-on DIN rail mount. Active lifecycle, ava","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"96 mm","Width":"45 mm","Height":"97 mm","Trip Class":"CLASS 10","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ed06380cd812569680d54f28d29c562.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=621339&mlfb=3RV6411-1JA10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RV6411-1JA10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RV6411-1JA10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RV6411-1JA10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}