{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW3016-1BB14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW3016-1BB14","canonicalUrl":"https://aoctrl.com/siemens/3RW3016-1BB14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW3016-1BB14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW3016-1BB14 soft starter, size S00, 9 A at 40 °C, 110–230 V DC control supply, integrated bypass contact system, screw-type terminals, screw and snap-on mounting.","salesMarkdown":"The Siemens SIRIUS 3RW3016-1BB14 is a size S00 soft starter rated 9 A at 40 °C, built for controlled motor starting in a 45 mm wide DIN-rail footprint. It carries an integrated bypass contact system, so once the motor is up to speed the thyristors are shorted out — no continuous heat dissipation from the power stack during run. That keeps the panel cool and extends the life of the surrounding components in a crowded enclosure. Clearance requirements: 60 mm upwards, 40 mm downwards, 15 mm at the side. The screw-type terminals on the main circuit and the auxiliary/control circuit accept 2x (0.25 to 2.5 mm²) solid conductors, with the front clamping point taking 2x (16 to 10) AWG. Wire length to the motor can run up to 300 m — fine for most pump and conveyor layouts on a mill floor. This is a soft starter, not a contactor — the thyristor ramp limits inrush current and mechanical shock on the load. The integrated bypass is the key differentiator from a basic starter: once the motor is at speed, the bypass contactor carries the full-load current, so the thyristors cool off. No separate bypass contactor to wire in the panel. The control supply accepts 110 to 230 V DC, which is wider than the typical 24 V DC on smaller SIRIUS soft starters, so it can share a control transformer with other 120 V or 220 V DC loads without a separate power supply. Derating is straightforward: 9 A at 40 °C, 8 A at 50 °C, 7 A at 60 °C. The minimum load is 10 % of the rated current, so it will not drop out on a lightly loaded motor. No motor overload protection built in — that needs to come from a separate overload relay or the drive's own thermal model. No adjustable current limitation, no inside-delta circuit, no external reset, no motor brake output. The red fault signal on the display gives a visual trip indication without needing to open the panel door.","metaTitle":"Siemens 3RW3016-1BB14 SIRIUS Soft Starter, 9A at 40°C","metaDescription":"Siemens SIRIUS 3RW3016-1BB14 soft starter, 9A rated at 40°C, 110-230V DC control, integrated bypass, size S00, screw terminals. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"150 mm","Width":"45 mm","Height":"95 mm","Mounting":"screw and snap-on mounting","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$143.51 – $244.65","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/08bd03615d49be9dbe020190c5354782.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=108570&mlfb=3RW3016-1BB14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW3016-1BB14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW3016-1BB14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW3016-1BB14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}