{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW3017-1BB04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW3017-1BB04","canonicalUrl":"https://aoctrl.com/siemens/3RW3017-1BB04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW3017-1BB04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS soft starter, 3RW3017-1BB04, size S00, 12.5 A at 40 °C, 24 V control voltage, integrated bypass contactor, screw and snap-on mounting.","salesMarkdown":"The Siemens 3RW3017-1BB04 is a SIRIUS soft starter in size S00, rated 12.5 A at 40 °C, derating to 12 A at 50 °C and 11 A at 60 °C. That 12.5 A figure is the continuous motor current it can ramp up without the thermal stress of a direct-on-line start — sized for a motor drawing roughly 5.5 to 7.5 kW at 400 V three-phase, depending on the load duty cycle. An integrated bypass contactor is built in, meaning once the motor reaches full speed the thyristors are shorted out. That eliminates SCR heat dissipation during run, so the enclosure doesn't need extra ventilation for continuous duty. The downside: no external reset input, so a fault trip requires a manual power cycle or a remote contactor ahead of it. Mounting is screw or snap-on onto a DIN rail, with 45 mm width and 95 mm height. Clearance requirements: 60 mm above, 40 mm below, 15 mm to the side. That's tighter than many soft starters in this class — useful for a crowded panel where every millimeter counts. This is a motor-starting component for a control panel, not a standalone drive. It ramps voltage to an induction motor over a set period, limiting inrush current. The operating temperature range of -25 to +60 °C covers most plant-floor conditions, but derating starts at 40 °C, so a hot cabinet near a furnace or oven needs the 50 °C or 60 °C current column. Main circuit connections are screw-type terminals; auxiliary and control circuits also use screw terminals. Solid wire range is 2x 0.25 to 2.5 mm². No inside-delta circuit configuration, so it's a standard in-line soft starter, not a six-wire delta-connected unit.","metaTitle":"Siemens 3RW3017-1BB04 SIRIUS Soft Starter, 12.5 A, Size S00","metaDescription":"Siemens 3RW3017-1BB04 SIRIUS soft starter, 12.5 A at 40 °C, size S00, 24 V control, integrated bypass. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Depth":"150mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45mm","title":"3RW3017-1BB04","Height":"95mm","Upwards":"60mm","Downwards":"40mm","Thyristors":"Yes","At The Side":"15mm","description":"SIRIUS soft starter S00 12.5 A, 5.5 kW/400 V, 40 °C 200-480 V AC, 24 V AC/DC Screw terminals","During Storage":"-40 ... +80°C","External Reset":"No","lifecycle_stage":"current","During Operation":"-25 ... +60°C","Fastening Method":"screw and snap-on mounting","Minimum Load [%]":"10%","Mounting Position":"With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° tiltable to the front and back","Product Brand Name":"SIRIUS","Degree Of Pollution":"3, acc. to IEC 60947-4-2","Product Designation":"Soft starter","Wire Length Maximum":"300m","Derating Temperature":"40°C","Inside-Delta Circuit":"No","at 50 Hz rated value":"24V","at 60 Hz rated value":"24V","at 40 °C rated value":"12.5A","at 50 °C rated value":"12A","at 60 °C rated value":"11A","For Auxiliary Contacts":"2x (20 ... 14)","For Main Current Circuit":"screw-type terminals","Motor Overload Protection":"No","Intrinsic Device Protection":"No","Adjustable Current Limitation":"No","Size Of Engine Control Device":"S00","Insulation Voltage Rated Value":"600V","Using The Front Clamping Point":"2x (16 ... 10)","Operating Frequency Rated Value":"50 ... 60Hz","Display Version For Fault Signal":"red","Integrated Bypass Contact System":"Yes","For Auxiliary And Control Circuit":"screw-type terminals","Product Component Motor Brake Output":"No","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","reference code according to EN 61346-2":"Q","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Evaluation Of Thermistor Motor Protection":"No","at standard circuit at 40 °C rated value":"5.5kW","at standard circuit at 50 °C rated value":"7.5hp","control supply voltage 1 at DC rated value":"24V","number of CO contacts for auxiliary contacts":"0","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"1","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Control Supply Voltage Frequency 1 Rated Value":"50Hz","Control Supply Voltage Frequency 2 Rated Value":"60Hz","Installation Altitude At Height Above Sea Level":"5 000m","continuous operating current [% of Ie] at 40 °C":"115%","Operating Voltage At Standard Circuit Rated Value":"200 ... 480V","contact rating of auxiliary contacts according to UL":"B300 / R300","Relative Negative Tolerance Of The Operating Frequency":"-10%","Relative Positive Tolerance Of The Operating Frequency":"10%","For Auxiliary Contacts Finely Stranded With Core End Processing":"2x (20 ... 16)","relative negative tolerance of the control supply voltage at DC":"-20%","relative positive tolerance of the control supply voltage at DC":"20%","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10%","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10%","Relative Negative Tolerance Of The Operating Voltage At Standard Circuit":"-15%","Relative Positive Tolerance Of The Operating Voltage At Standard Circuit":"10%","power loss [W] at operational current at 40 °C during operation typical":"2W","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-15%","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-15%","relative positive tolerance of the control supply voltage at AC at 50 Hz":"10%","relative positive tolerance of the control supply voltage at AC at 60 Hz":"10%"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$244.98","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1290f296a4e2f882e1874b6afcb80c17.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=66337&mlfb=3RW3017-1BB04"},"ai":{"faq":[{"question":"What are the key dimensions and clearances for 3RW3017-1BB04?","answer":"Width 45 mm, height 95 mm, depth 150 mm. Required clearances: 60 mm above, 40 mm below, 15 mm to the side."},{"question":"Does 3RW3017-1BB04 have an integrated bypass contactor?","answer":"Yes, an integrated bypass contactor is built in, which shorts the thyristors once the motor reaches full speed, eliminating SCR heat during continuous run."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW3017-1BB04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW3017-1BB04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}