{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4046-1BB14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4046-1BB14","canonicalUrl":"https://aoctrl.com/siemens/3RW4046-1BB14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4046-1BB14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4046-1BB14 soft starter, Size S3, 80 A at 40 °C, screw-type terminals, 110 … 230 V DC control supply, thyristor-based.","salesMarkdown":"It delivers adjustable current limitation and built-in motor overload protection, with an external reset input for remote fault recovery. The control supply accepts 110 … 230 V DC, and the operating frequency is 50 … 60 Hz. Rated current derates with ambient: 73 A at 50 °C, 66 A at 60 °C. The 20% minimum load setting prevents nuisance tripping on lightly loaded motors. Fastens via screw and snap-on mounting. Dimensions: 70 mm wide, 170 mm high, 190 mm deep. Clearance requirements: 60 mm above, 40 mm below, 30 mm at the sides. With an additional fan, the mounting surface can be vertical and rotated ±90° or tilted ±22.5° front/back; without a fan, rotation and tilt are limited to ±10°. Main circuit uses screw-type terminals. Solid wire: 2x (0.5 … 2.5 mm²). Stranded: 2x (10 … 70 mm²). Finely stranded: 2x (10 … 50 mm²). Auxiliary contacts accept 2x (20 … 14 AWG). Maximum wire length to motor: 300 m.","metaTitle":"Siemens 3RW4046-1BB14 SIRIUS Soft Starter, 80A, Size S3","metaDescription":"Siemens SIRIUS 3RW4046-1BB14 soft starter, 80A at 40°C, Size S3, screw terminals, 110-230V DC control supply. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Depth":"190mm","Solid":"2x (0.5 ... 2.5 mm²)","Width":"70mm","title":"3RW4046-1BB14","Height":"170mm","Upwards":"60mm","Stranded":"2x (10 ... 70 mm²)","Downwards":"40mm","Thyristors":"Yes","At The Side":"30mm","description":"SIRIUS soft starter S3 80 A, 45 kW/400 V, 40 °C 200-480 V AC, 110-230 V AC/DC Screw terminals","During Storage":"-40 ... +80°C","External Reset":"Yes","Finely Stranded":"2 x (10 ... 50 mm²)","lifecycle_stage":"current","During Operation":"-25 ... +60°C","Fastening Method":"screw and snap-on mounting","Minimum Load [%]":"20%","For Main Contacts":"2x (7 ... 1/0)","Mounting Position":"With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t","Product Brand Name":"SIRIUS","Degree Of Pollution":"3, acc. to IEC 60947-4-2","Product Designation":"Soft starter","Wire Length Maximum":"300m","Derating Temperature":"40°C","Inside-Delta Circuit":"No","at 40 °C rated value":"80A","at 50 °C rated value":"73A","at 60 °C rated value":"66A","For Auxiliary Contacts":"2x (20 ... 14)","For Main Current Circuit":"screw-type terminals","Motor Overload Protection":"Yes","Using Both Clamping Points":"10 ... 2/0","Intrinsic Device Protection":"Yes","Adjustable Current Limitation":"Yes","Size Of Engine Control Device":"S3","Using The Back Clamping Point":"2x (10 ... 1/0)","Insulation Voltage Rated Value":"600V","Using The Front Clamping Point":"2x (10 ... 1/0)","control supply voltage 1 at DC":"110 ... 230V","Operating Frequency Rated Value":"50 ... 60Hz","Display Version For Fault Signal":"red","Integrated Bypass Contact System":"Yes","For Auxiliary And Control Circuit":"screw-type terminals","Product Component Motor Brake Output":"No","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","reference code according to EN 61346-2":"Q","control supply voltage 1 at AC at 50 Hz":"110 ... 230V","control supply voltage 1 at AC at 60 Hz":"110 ... 230V","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Evaluation Of Thermistor Motor Protection":"No","at standard circuit at 40 °C rated value":"45kW","at standard circuit at 50 °C rated value":"50hp","number of CO contacts for auxiliary contacts":"1","number of NC contacts for auxiliary contacts":"0","number of NO contacts for auxiliary contacts":"2","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Control Supply Voltage Frequency 1 Rated Value":"50Hz","Control Supply Voltage Frequency 2 Rated Value":"60Hz","Installation Altitude At Height Above Sea Level":"5 000m","continuous operating current [% of Ie] at 40 °C":"115%","Operating Voltage At Standard Circuit Rated Value":"200 ... 480V","contact rating of auxiliary contacts according to UL":"B300 / R300","Relative Negative Tolerance Of The Operating Frequency":"-10%","Relative Positive Tolerance Of The Operating Frequency":"10%","For Auxiliary Contacts Finely Stranded With Core End Processing":"2x (20 ... 16)","relative negative tolerance of the control supply voltage at DC":"-15%","relative positive tolerance of the control supply voltage at DC":"10%","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10%","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10%","Relative Negative Tolerance Of The Operating Voltage At Standard Circuit":"-15%","Relative Positive Tolerance Of The Operating Voltage At Standard Circuit":"10%","power loss [W] at operational current at 40 °C during operation typical":"12W","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-15%","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-15%","relative positive tolerance of the control supply voltage at AC at 50 Hz":"10%","relative positive tolerance of the control supply voltage at AC at 60 Hz":"10%","Adjustable Motor Current For Motor Overload Protection Minimum Rated Value":"43A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,269.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7fc09c81ba4f9ca7ddf107ab66b808d1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=183384&mlfb=3RW4046-1BB14"},"ai":{"faq":[{"question":"What are the key ratings for this soft starter?","answer":"Rated 80 A at 40 °C, 73 A at 50 °C, 66 A at 60 °C. Control supply 110 … 230 V DC. Insulation voltage 600 V. Operating frequency 50 … 60 Hz. Minimum load 20%."},{"question":"What wire sizes does the 3RW4046-1BB14 accept?","answer":"Main circuit screw terminals accept solid 2x (0.5 … 2.5 mm²), stranded 2x (10 … 70 mm²), and finely stranded 2x (10 … 50 mm²). Auxiliary contacts accept 2x (20 … 14 AWG)."},{"question":"What clearance is needed around the 3RW4046-1BB14?","answer":"60 mm above, 40 mm below, 30 mm at the sides. Mounting position depends on whether an additional fan is used — with fan, rotation up to ±90° and tilt ±22.5°; without fan, ±10°."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4046-1BB14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4046-1BB14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}