{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4046-1TB04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4046-1TB04","canonicalUrl":"https://aoctrl.com/siemens/3RW4046-1TB04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4046-1TB04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4046-1TB04 soft starter, 80 A at 40 °C, S3 frame size, 600 V insulation voltage, screw-type terminals, 50/60 Hz.","salesMarkdown":"## 80 A at 40 °C — the rating that governs the panel The 3RW4046-1TB04: That 40 °C base is the typical unventilated enclosure ceiling — if your panel runs hotter, the usable current drops by roughly 9 % per 10 °C rise. It carries a 600 V insulation voltage rating (pollution degree 3 per IEC 60947-4-2), which covers 480 V and 575 V line supplies common in North American and European industrial plants. ## Mounting and clearance — S3 frame realities The S3 frame measures 170 mm high, 70 mm wide, and 190 mm deep. It mounts via screw and snap-on to DIN rail — the snap-on lets you pre-wire the panel and clip the unit in last. Clearance matters: 60 mm above, 40 mm below, and 30 mm at the side for airflow. Without an additional fan, the mounting surface must stay within ±10° of vertical and ±10° tilt. With the optional fan, the envelope opens to ±90° rotation and ±22.5° tilt front/back. ## Terminal capacity and wiring Main circuit terminals accept screw-type connections: 2x (10 … 70 mm²) stranded or 2x (10 … 50 mm²) finely stranded, plus 2x (7 … 1/0) AWG for the main contacts. Maximum motor cable length is 300 m — long enough for most pump and conveyor runs, but if you're feeding a motor 400 m away, plan on an output reactor or derating the cable capacitance. ## Protection and control features Built-in motor overload protection and intrinsic device protection are standard. The adjustable current limitation (20 % minimum load) lets you tune the starting torque to the load — useful for soft-starting high-inertia fans or conveyors without tripping upstream breakers. The unit uses thyristor-based soft-start technology — no inside-delta circuit option on this variant. The derating temperature threshold is 40 °C — above that, the continuous current rating steps down as shown in the spec table.","metaTitle":"Siemens 3RW4046-1TB04 SIRIUS Soft Starter, 80 A, S3 Frame","metaDescription":"Siemens 3RW4046-1TB04 SIRIUS soft starter, 80 A at 40 °C, S3 frame, 600 V insulation. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"190 mm","Width":"70 mm","Height":"170 mm","Mounting":"screw and snap-on mounting","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$805.18","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9e5014c226494640b47cca1d31f13cc4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=524045&mlfb=3RW4046-1TB04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4046-1TB04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4046-1TB04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4046-1TB04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}