{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4056-6BB35","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4056-6BB35","canonicalUrl":"https://aoctrl.com/siemens/3RW4056-6BB35","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4056-6BB35","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4056-6BB35 soft starter, Size S6, 162 A at 40 °C, 50/60 Hz, screw fixing, 250 mm depth, 120 mm width, 198 mm height.","salesMarkdown":"## Panel fit and frame dimensions The 3RW4056-6BB35 sits in the SIRIUS Size S6 frame — 250 mm deep, 120 mm wide, 198 mm tall — which sets the minimum enclosure depth for a backpanel layout. Screw fixing to the mounting plate; no DIN-rail snap-on here, so plan for drilled and tapped holes or a sub-panel. Clearance around the unit: 100 mm above, 75 mm below, 5 mm at the sides. That 75 mm bottom gap is the one that catches people — skimp on it and the power cables won't bend into the terminals without strain. ## Current ratings and thermal derating Headline rating is 162 A at 40 °C ambient — that's the number for a standard 40 °C panel environment. The derating temperature threshold is 40 °C, so above that the continuous current falls linearly. For a motor starting application, the inrush duty is brief, but the thermal model in the soft starter tracks the I²t accumulation across starts. Minimum load is 20 % of the rated current — below that the soft starter may not detect the motor load correctly. Adjustable current limitation is built in, so you can set the start current ceiling below the full 162 A to match the supply transformer or generator capacity. ## Termination and conductor sizing Main circuit connection uses busbar or cable lugs — the terminal accepts 4 AWG to 250 kcmil (25–120 mm² stranded) at the front and back clamping points, and 2x 1/0 max using both points. For auxiliary control wiring, solid or finely stranded 0.5–2.5 mm² (20–14 AWG) is the range. The busbar connection option is worth noting for panel builders who want a clean power distribution bar rather than individual cable tails. Maximum motor cable length is 300 m — beyond that the cable capacitance can cause nuisance tripping or affect the soft starter's firing angle control, especially on long runs to remote pumps or conveyors. ## Environmental and compliance Pollution degree 3 per IEC 60947-4-2 — this is the industrial default: conductive pollution or dry non-conductive pollution that becomes conductive due to condensation. The mounting position has restrictions: with the optional fan the unit can be rotated ±90° on a vertical surface and tilted ±22.5° front-to-back; without the fan the rotation is limited to ±10°.","metaTitle":"Siemens 3RW4056-6BB35 SIRIUS Soft Starter, 162A, Size S6","metaDescription":"Siemens 3RW4056-6BB35 SIRIUS soft starter, 162A at 40°C, Size S6 frame, 250mm depth. Active production, screw-fix mounting, pollution degree 3. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"250 mm","Width":"120 mm","Height":"198 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,508.25","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/57d025292b89620d9abd28e73ba01e5f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=491965&mlfb=3RW4056-6BB35","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4056-6BB35/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4056-6BB35","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4056-6BB35 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}