{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4074-2BB35","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4074-2BB35","canonicalUrl":"https://aoctrl.com/siemens/3RW4074-2BB35","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4074-2BB35","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4074-2BB35 soft starter, Size S12, 280 A at 40 °C, 115 V control, 50/60 Hz, screw fixing, busbar connection.","salesMarkdown":"## 280 A continuous — the rating that sizes the motor branch The 3RW4074-2BB35: That 280 A figure is the base continuous current that sizes the motor branch — the contactor, overload relay, and cable all follow from it. The 600 V insulation voltage sets the system voltage ceiling; the 50/60 Hz operating frequency covers global line frequencies without a hardware change. Motor overload protection is built in, and the adjustable current limitation lets you tune the starting current to the load — useful for pumps or conveyors where a hard start stresses the drivetrain. The minimum load is 20 %, so it handles lightly loaded motors without tripping on undercurrent. ## Panel fit — Size S12, busbar connection, 115 V control The S12 frame measures 278 mm deep, 160 mm wide, and 230 mm high. Screw fixing to the mounting surface — no DIN rail clip. The main current circuit uses busbar connection with a clamping range of 2/0 to 500 kcmil using both clamping points, or 250 to 500 kcmil at the back point and 3/0 to 600 kcmil at the front. Stranded wire for the main circuit is 70 to 240 mm²; finely stranded 50 to 240 mm². Auxiliary contacts accept 2x (24 to 16) AWG; solid wire for aux circuits is 2x (0.25 to 1.5 mm²). The maximum wire length to the motor is 300 m — keep that in mind for remote motor installations where voltage drop matters. ## Ambient and mounting constraints The derating temperature is 40 °C — above that, the continuous current drops as shown in the derating steps. Mounting position: with an additional fan, the unit can be mounted on a vertical surface with +/-90° rotation and +/-22.5° tilt front/back. Without the fan, rotation is limited to +/-10° and tilt to +/-10°. Clearances: 100 mm upward, 75 mm downward, and 5 mm at the sides. The side clearance is tight — plan the gland plate and busbar routing accordingly.","metaTitle":"Siemens 3RW4074-2BB35 SIRIUS Soft Starter, 280 A, Size S12","metaDescription":"Siemens 3RW4074-2BB35 SIRIUS soft starter, 280 A at 40 °C, 600 V insulation, Size S12. Current production — quoted to order against your BOM. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"278 mm","Width":"160 mm","Height":"230 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb10fd7cdc9b0f716cefa5a226848a22.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=459270&mlfb=3RW4074-2BB35","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4074-2BB35/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4074-2BB35","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4074-2BB35 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}