{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4074-6BB34","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4074-6BB34","canonicalUrl":"https://aoctrl.com/siemens/3RW4074-6BB34","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4074-6BB34","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4074-6BB34 soft starter, Size S12, 280 A at 40 °C, 50/60 Hz, 115 V control voltage, screw fixing, busbar connection.","salesMarkdown":"## What the 280 A rating means for motor sizing The 3RW4074-6BB34: The 280 A at 40 °C is the continuous rated current for the soft starter's main thyristors — this is the number you size against the motor FLA, not the upstream breaker. The derating temperature is 40 °C, meaning the full 280 A is only available up to that ambient; above it the current drops per the datasheet curve. The adjustable current limitation lets you set a starting current ceiling below the motor's locked-rotor draw — useful when the supply transformer or generator is undersized and you need to limit voltage dip during start. Minimum load is 20%, so it handles lightly loaded motors without dropping out. ## Panel integration and wiring constraints Size S12 means a 230 mm height, 160 mm width, and 278 mm depth — that's a substantial block, so plan the enclosure depth accordingly. Screw fixing to the mounting plate, not DIN rail; the fastening method is four screws into the back panel. Clearance: 100 mm above, 75 mm below, 5 mm at the sides — the side gap is tight, so adjacent components need to be low-heat or spaced further if the ambient stacks. Main circuit termination is busbar connection — not cable lugs on the standard version. Stranded wire range is 70 to 240 mm², finely stranded 50 to 240 mm². For the US market, the main contacts accept 2/0 to 500 kcmil, with the back clamping point taking 250 to 500 kcmil and the front clamping point 3/0 to 600 kcmil. ## Environmental and protection features Pollution degree 3 per IEC 60947-4-2 — that's the industrial environment with conductive pollution, so no additional conformal coating is required for typical panel conditions. Insulation voltage rated 600 V. Motor overload protection is built in — no separate overload relay needed. Intrinsic device protection covers the soft starter's own thyristors against over-temperature and over-current. External reset allows remote fault recovery without opening the panel door.","metaTitle":"Siemens 3RW4074-6BB34 SIRIUS Soft Starter, 280A at 40°C","metaDescription":"Siemens 3RW4074-6BB34 SIRIUS soft starter, 280A rated at 40°C, Size S12 frame, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"278 mm","Width":"160 mm","Height":"230 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/863154563ecb878e7dd48de7f1119947.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=75659&mlfb=3RW4074-6BB34","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4074-6BB34/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4074-6BB34","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4074-6BB34 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}