{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4423-3BC46","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4423-3BC46","canonicalUrl":"https://aoctrl.com/siemens/3RW4423-3BC46","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4423-3BC46","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4423-3BC46 soft starter, 62 A at 40 °C, 690 V insulation voltage, integrated bypass contact system, thyristor-based.","salesMarkdown":"The Siemens SIRIUS 3RW4423-3BC46 is a thyristor-controlled soft starter with an integrated bypass contact system, rated for motor starting applications where reduced inrush and controlled acceleration are needed. The bypass contact system closes after start-up, shunting the thyristors to eliminate heat dissipation during run — a feature that matters in high-duty-cycle or enclosed-panel installations where every watt of waste heat has to be managed. Rated current is 62 A at 40 °C, derating to 55 A at 50 °C and 50 A at 60 °C. The 62 A figure governs the motor FLA it can start; if your motor plate says 60 A FLA at 40 °C ambient, this part fits. Above 40 °C, use the derated values for the actual panel ambient. Adjustable current limitation is built in, and the minimum load is 8% of the rated current — useful when the connected motor is small relative to the starter rating. Mounting is screw fixing onto a vertical surface, rotatable ±90° and tiltable ±22.5° front-to-back. Clearances: 100 mm above, 75 mm below, 5 mm at the sides. Depth is 270 mm, width 170 mm, height 192 mm — factor that into your gland-plate layout and panel depth. Main current circuit uses box terminals accepting solid 2x (0.25... 1.5 mm²) or stranded 2x (4... 50 mm²). Auxiliary and control circuits use spring-loaded terminals for 2x (24... 16) AWG. Maximum wire length is 500 m. ## Thermal and Environmental Limits Operating ambient temperature during operation is 60 °C; storage range is -25 to +80 °C. Derating begins above 40 °C. Intrinsic device protection and motor overload protection are integrated, with an external reset option and a display for fault signals.","metaTitle":"Siemens 3RW4423-3BC46 SIRIUS Soft Starter, 62 A, 690 V, inte","metaDescription":"Siemens SIRIUS 3RW4423-3BC46 soft starter. 62 A at 40°C, 690 V insulation voltage, integrated bypass, thyristor-controlled. Current production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"270 mm","Width":"170 mm","Height":"192 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,116.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/917484989a61b114073ab37fa830fb15.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=4506&mlfb=3RW4423-3BC46","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4423-3BC46/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4423-3BC46","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4423-3BC46 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}