{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4427-3BC36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4427-3BC36","canonicalUrl":"https://aoctrl.com/siemens/3RW4427-3BC36","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4427-3BC36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4427-3BC36 soft starter, 161 A at 40 °C, 690 V insulation voltage, 50/60 Hz, integrated bypass, adjustable current limitation, inside-delta circuit, screw fixing.","salesMarkdown":"## Current derating and thermal budget The 3RW4427-3BC36: Minimum load is 8 % of the rated current — below that the soft starter may not trigger the thyristors reliably, so check the motor magnetising current against this floor. ## Bypass and protection topology Integrated bypass contact system means the thyristors are shorted out after start, eliminating continuous conduction losses — the 161 A rating applies to the bypass path, not just the silicon. Built-in motor overload protection and intrinsic device protection reduce external relay count; adjustable current limitation lets you set the start ramp ceiling without a separate current-limiting reactor. ## Wiring and panel fit Envelope is 170 mm wide, 192 mm high, 270 mm deep — screw fixing, not DIN rail. Mounting position allows ±90° rotation and ±22.5° tilt front-to-back, which helps in tight retrofit cabinets. Clearance: 100 mm upward, 75 mm downward, 5 mm at the sides — the side gap is tight; forced airflow or a wider cabinet may be needed above 40 °C. ## Inside-delta wiring and motor lead length Inside-delta circuit configuration is supported — this places the soft starter in the delta legs of a six-lead motor, reducing the current rating needed by about 58 % compared to in-line wiring. Useful for retrofitting a smaller unit onto an existing motor. Maximum motor cable length is 500 m — beyond that, reflected wave voltage spikes at the motor terminals may exceed the thyristor blocking voltage, especially on 690 V systems. ## Environmental and compliance Pollution degree 3 per IEC 60947-4-2 — conductive pollution or dry non-conductive pollution that becomes conductive due to condensation is expected. The enclosure seal and internal creepage distances are designed for this. Storage temperature range -25 to +80 °C; operation up to 60 °C ambient. Insulation voltage rated 690 V, operating frequency 50/60 Hz.","metaTitle":"Siemens 3RW4427-3BC36 SIRIUS Soft Starter, 161 A, 690 V","metaDescription":"Siemens 3RW4427-3BC36 SIRIUS soft starter, 161 A at 40 °C, 690 V insulation, 50/60 Hz. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"270 mm","Width":"170 mm","Height":"192 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f1c83b3fad163120b0ed172f06af9d6a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=41810&mlfb=3RW4427-3BC36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4427-3BC36/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4427-3BC36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4427-3BC36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}