{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4434-2BC35","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4434-2BC35","canonicalUrl":"https://aoctrl.com/siemens/3RW4434-2BC35","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4434-2BC35","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4434-2BC35 soft starter, 196 A at 40 °C, 690 V insulation voltage, 50/60 Hz, inside-delta circuit, adjustable current limitation, motor overload protection, screw fixing.","salesMarkdown":"The 3RW4434-2BC35: The 690 V insulation voltage per IEC 60947-4-2 means it handles 400 V and 480 V systems with headroom — the pollution degree 3 rating confirms it tolerates conductive dust and condensation typical in industrial panels without requiring conformal coating on the power board. The inside-delta circuit connects the thyristors in the motor delta legs rather than the supply lines, reducing the current each thyristor carries by roughly 58 % compared to a standard in-line soft starter. This means the 196 A unit can start a motor with a nominal FLA up to about 340 A when wired inside-delta — a key spec for a panel builder sizing the starter to the motor nameplate, not the line current. ## Mounting and wiring — what ships in the carton Screw fixing with a vertical mounting surface that is rotatable ±90° and tiltable ±22.5° front-to-back — the unit fits into a panel without a dedicated mounting bracket. Dimensions are 200 mm high, 170 mm wide, 270 mm deep. The main circuit connection accepts busbar or cable: stranded 25–120 mm², finely stranded 16–95 mm², or 4–250 kcmil. Auxiliary contacts take 2× (24–16) AWG and solid 2× (0.25–1.5 mm²). The kit is complete — no missing gland plates or adapter rails. Clearance distances: 100 mm upward, 75 mm downward, 5 mm at the side. The maximum motor cable length is 500 m — long enough for most pump and conveyor runs without adding output reactors. ## Protection and control — what the soft starter handles internally Built-in motor overload protection and intrinsic device protection mean the 3RW4434-2BC35 does not require a separate overload relay in most installations — the soft starter monitors motor current and trips on overload. Adjustable current limitation sets the starting current between 0 and the rated current, protecting both the motor and the supply transformer during acceleration. Minimum load is 8 % of the rated current — it will not drop out on lightly loaded motors. External reset allows a remote pushbutton or PLC output to clear a fault without opening the panel. A display version for fault signal shows the trip cause locally.","metaTitle":"Siemens 3RW4434-2BC35 SIRIUS Soft Starter, 196 A, 690 V","metaDescription":"Siemens 3RW4434-2BC35 SIRIUS soft starter, 196 A at 40 °C, 690 V insulation. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"270 mm","Width":"170 mm","Height":"200 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/06a9addc3dc7d93277a8d7e59fc24767.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=196459&mlfb=3RW4434-2BC35","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4434-2BC35/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4434-2BC35","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4434-2BC35 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}